Fast delivery within 72 Hours
Acim Nidec LSAH 44.3 – Cogeneration alternator | 40 – 94 kVA
Built to heat
The LSAH range of alternators has been designed to maximize efficiency of cogeneration installations.
Thanks to its specific builtâin coolant circuit, heat recovery is optimized and d…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Built to heat
The LSAH range of alternators has been designed to maximize efficiency of cogeneration installations.
Thanks to its specific builtâin coolant circuit, heat recovery is optimized and directly fed into the larger installation. LSAH alternators are also perfectly suited for continuous service connected to the national grid and other applications like oil and gas. The various design elements and construction features of LSAH machines make them highly performant and durable
Electrical features & performances
Class H insulation
2/3 pitch winding, standard 6-wire (6S) reconnectable
Voltage range:
50 Hz: 380V/400V/415V
60 Hz: 380V/440V/480V
Other voltages: consult us
High efficiency and motor starting capacity
Mechanical construction
Compact rigid assembly to better withstand generator vibrations
Steel frame and terminal box
Cast iron flanges and shields
Two-bearing and single bearing mounting
Half-key balancing
Ball bearings greasable 40,000h
Direction of rotation: clockwise and anti-clockwise (without derating)
Noise level: 81 dBA (IEC 60034-9)
Output cable direction: left or right
Terminal box design
Remote voltage regulator (AVR not mounted in terminal box)
Terminal block for voltage reconnection
Terminal block on the left or right, or both sides (with extra cost)
Specification
| Insulation class |
H H |
|---|---|
| Winding pitch |
2/3 (winding 6S – 6-wire) 2/3 (winding 6S – 6-wire) |
| Number of wires |
6 6 |
| Protection |
IP44 IP44 |
| Cooling - Code |
Water – IC7A1W7 Water – IC7A1W7 |
| Altitude |
≤ 1000 m ≤ 1000 m |
| Overspeed |
2250 min-1 2250 min-1 |
| Water flow |
3 to 10 m3/h 3 to 10 m3/h |
| Excitation system |
AREP AREP |
| AVR type |
D350 D350 |
| Voltage regulation (Steady state) |
± 0,25 % ± 0,25 % |
| Short-circuit current |
300 % (3IN) : 10s 300 % (3IN) : 10s |
| Total Harmonic Distortion THD (*) in no-load |
< 2 % < 2 % |
| Total Harmonic Distortion THD (*) in linear load |
< 5 % < 5 % |
| Waveform: NEMA = TIF (*) |
< 50 % < 50 % |
| Waveform: I.E.C. = THF (*) |
< 1.5 % < 1.5 % |
| Regulators |
D550 D350 |
| AREP |
â â |
| Mains Paralleling |
â – |
| 3-phase sensing |
â â |
| Remote voltage potentiometer |
â â |
| Current transformer for paralleling |
â â |

Reviews
Clear filtersThere are no reviews yet.