Fast delivery within 72 Hours

Beckhoff EP3162-0002

The EP3162-0002 EtherCAT Box has two analog inputs which can be individually parameterized, so that they process signals either in the -10/0…+10 V or the -20/0/4…+20 mA range. The voltage or input cur…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

The EP3162-0002 EtherCAT Box has two analog inputs which can be individually parameterized, so that they process signals either in the -10/0…+10 V or the -20/0/4…+20 mA range. The voltage or input current is digitized with a resolution of 16 bits, and is

Specification

ProtocolEtherCAT
Bus Interface2 x M8 socket, 4-pin, a-coded, shielded
Number Of Inputs2 (single-ended)
Input ConnectionsM12 x 1, 5-pin, a-coded
Conversion Time~ 100 µs
Resolution16 bit (incl. sign)
Signal Type-10/0…+10 V, -20/0/4…+20 mA, parameterizable per channel
Common Mode Voltage Ucmmax. 35 V
Internal Resistance> 200 kΩ, typ. 85 Ω + diode voltage
Measurement Error/Uncertainty±0.3% (relative to full scale value)
Input Filter Limit Frequency5 kHz
Nominal Voltage24 V DC (-15%/+20%)
Distributed Clocksyes
Input Filterconfigurable
Sensor SupplyUA from US, electrically isolated
Current Consumption From Us120 mA
Power Supply Connectionfeed: 1 x M8 male socket, 4-pin, a-coded; downstream connection: 1 x M8 female socket, 4-pin, a-coded
Electrical Isolation500 V fieldbus, 300 V signals/signal
Special Featuresgalvanic isolation of the channels
Weightapprox. 165 g
Operating Temperature-25…+60°C
Storage Temperature-40…+85°C
Vibration/Shock Resistanceconforms to EN 60068-2-6/EN 60068-2-27
Emc Immunity/Emissionconforms to EN 61000-6-2/EN 61000-6-4
Protect. Rating/Installation Pos.IP65/66/67 (conforms to EN 60529)/variable
Approvals/MarkingsCE, UL, ATEX, IECEx
Ex MarkingATEX: II 3 G Ex ec IIC T4 Gc II 3 D Ex tc IIIC T135 °C Dc IECEx: Ex ec IIC T4 Gc Ex tc IIIC T135 °C Dc
Dimensions (W X H X D)30 mm x 126 mm x 26.5 mm
MaterialPA6 (polyamide)
Installation2 fixing holes 3.5 mm diameter for M3

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Beckhoff EP3162-0002”