Fast delivery within 72 Hours

Wago 857-815

Short description:WAGO’s loop-powered RTD temperature signal conditioner records sensors (Pt100, Pt200, Pt500, Pt1000) and resistors up to 4.5 kΩ, converting the temperature signal into a standard ana…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Short description:WAGO’s loop-powered RTD temperature signal conditioner records sensors (Pt100, Pt200, Pt500, Pt1000) and resistors up to 4.5 kΩ, converting the temperature signal into a standard analog signal at the output.The loop-powered RTD temperature signal conditioner provides safe isolation between input and output with 3 kV test voltage per EN 61010-1.Features:No additional supply voltage requiredFor Pt100, Pt200, Pt500 and Pt1000 sensors, as well as resistors up to 4.5 kOhm2-, 3- and 4-wire connection technologyCalibrated measurement range switchingDetects a sensor wire break/short circuit

Specification

Notes

Safety InformationThe signal conditioner must only be configured with the DIP switch in the de-energized state.
NoteUse shielded signal cables!Only use shielded signal cables for analog input and output signals.This ensures the device maintains its specified accuracy and immunity to interference, even when external disturbances affect the signal cable.

Technical data - Configuration

Configuration optionsDIP switch

Technical data - Input

Input signal typeResistance, Pt sensors, Resistor

Technical data - Input (RTD sensors)

Sensor types (RTD)Pt100, Pt200, Pt500, Pt1000
Sensor connection2-wire; 3-wire; 4-wire (switchable)
Sensor power supply (RTD) max.≤ 0.5 mA
Temperature measurement range (RTD)−200 … +850 °C
Measurement span (RTD) min.50 K

Technical data - Input (resistors)

Input range (resistor)0 … 1 kΩ; 0 … 4.5 kΩ

Technical data - Output (analog)

Output signal typeCurrent
Output signal (current)4 … 20 mA, 20 … 4 mA
Load impedance (current output)See derating graphic

Technical data - Signal processing

Step response (typ.)1000 ms

Technical data - Measurement error

Transmission error (typ.)≤ 0.1 % at full measurement span
Transmission error for the set measurement range≤ ((40 K/set measurement range [K]) + 0.1) %
Transmission error (under interference)≤ 5 %
Temperature coefficient≤ 0.02 %/K

Technical data - Power supply

Power supply typeLoop-powered (via output)
Supply voltage8 … 30 VDC (Power is derived from the output circuit.)
Power loss (max.) P<sub>l (max.)</sub>0.7 W

Safety and protection

Rated voltage300 V; 150 V (UL)
Measurement category per EN/UL 61010-2-030CAT II (input)
Protection typeIP20

Safety and protection - Test voltage

Test voltage (input/analog output)3 kVAC; 50 … 60 Hz; 1 min

Safety and protection - Insulation coordination (UL)

Overvoltage categoryII
Pollution degree2
Insulation type (input/analog output)Reinforced insulation (safe isolation)

Safety and protection - Insulation coordination

Overvoltage categoryII
Pollution degree2
Insulation type (input/analog output/supply)Reinforced insulation (safe isolation)

Connection data

Connection technologyPush-in CAGE CLAMP®
Solid conductor0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor0.34 … 2.5 mm² / 22 … 14 AWG
Strip length9 … 10 mm / 0.35 … 0.39 inches

Physical data

Width6 mm / 0.236 inches
Height94 mm / 3.701 inches
Depth from upper-edge of DIN-rail97.8 mm / 3.85 inches

Mechanical data

Mounting typeDIN-35 rail

Material data

Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Fire load0.013 MJ
Weight38.9 g

Environmental requirements

Ambient temperature (operation)-25 … +70 °C
Ambient temperature (storage)-40 … +85 °C
Temperature range of connection cable≥ (Tambient + 10 K)
Temperature range of the connection cable (UL)75 °C
Relative humidity5 … 95 % (no condensation permissible)
Operating altitude (max.)2000 m

Standards and specifications

Conformity markingCE
EMC immunity to interferenceEN 61000-6-2; EN 61326-1; EN 50121-3-2
EMC emission of interferenceEN 61000-6-3; EN 61326-1; EN 50121-3-2
Standards/specificationsEN 61010-1, EN 61373

Commercial data

PU (SPU)1 pcs
Packaging typebag
Country of originDE
GTIN4055143475648
Customs tariff number85437090300

Product Classification

UNSPSC41111970
eCl@ss 10.027-21-01-29
eCl@ss 9.027-21-01-29
ETIM 9.0EC002919
ETIM 10.0EC002919
ECCNNO US CLASSIFICATION

Environmental Product Compliance

CAS-No.1303-86-2, 1317-36-8, 7439-92-1, 75980-60-8, 79-94-7
REACH Candidate List Substance2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol, Diboron trioxide, Lead, Lead monoxide, Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)-
RoHS Compliance StatusCompliant,No Exemption
RoHS Exemption6(c), 7(a), 7(c)-I, 7(c)-II
SCIP notification number (Austria)830a7e26-28ea-4705-ab6e-226f9c633520
SCIP notification number (Belgium)63788937-7a1f-4563-936a-f01960202294
SCIP notification number (Bulgaria)7573483d-d923-4363-9064-ce0784b75504
SCIP notification number (Czech Republic)17fdd5aa-0c9d-4035-8fac-fb4e34ddac7f
SCIP notification number (Denmark)f6a88738-2c30-4e26-8f7e-78d92a8961e5
SCIP notification number (Finland)b4ce184e-8252-4b06-b805-6aa2c771805f
SCIP notification number (France)7d65f4e8-4b0d-4e4d-922c-5b4b37ec9f15
SCIP notification number (Germany)7eda7375-97a9-4708-8499-ee382843832f
SCIP notification number (Hungary)eef5d1bb-60c8-4a7b-815f-42f57a0b5106
SCIP notification number (Italy)9d811551-d172-4095-9c09-acc10881822b
SCIP notification number (Netherlands)5b4bce60-08c5-43bc-b361-c0de92c2e4da
SCIP notification number (Poland)05d900c2-b348-49b3-9862-d1595b7b0a8f
SCIP notification number (Romania)5914960a-62a8-45a9-95fc-a9ee80aab951
SCIP notification number (Sweden)d4592a7f-9ffa-4c4d-9de5-be795739849b

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Wago 857-815”

Your email address will not be published. Required fields are marked *