Distribution connector WINSTA® MIDI rated current 25 AUse effective pluggable connections instead of laborious screw connections: With the WINSTA® MIDI distribution connector with protection against mismating. WAGO pluggable installation connectors are used when criteria repeat or are distributed on a specified pattern, for example for installing grid lighting or flush-mount lighting. For greater security in electrical installations, the pluggable installation connector is equipped with mechanical protection against mismating. The pluggable installation connector is protected in accordance with protection type IP20 (When mated: IP2xC (These compact connectors are not designed for use in open, easily accessible areas!)). This means that users’ fingers will never come into contact with energised contact elements. Solutions like the WINSTA® MIDI pluggable installation connectors with B coding are suitable for process control, such as for lighting or in data networks. This pluggable installation connector is used for electrical currents up to 25 A. Thus the product is also suitable for high power loads. WINSTA® MIDI with Push-in CAGE CLAMP® spring pressure connection technology is used in can be found in a variety of projects you can use for quick, easy, flexible, and secure installation.Lower costs through fast commissioning and elimination of service expenses – solutions from WINSTA® MIDIThe WINSTA® Pluggable Connection System allows pluggable electrical installation. This saves time, lowers costs, and reduces the need for servicing. Now you can also reduce installation expenses without compromising safety and quality: with locking lever reduces the need for servicing and prevents unnecessary downtime. protection against mismating eliminates errorssimple circuitsfor automation controllersready for immediate useconvenient installation and commissioning

Specification

Notes

Variants:Other pole markings, Other versions (or variants) can be requested from WAGO Sales or configured at https://configurator.wago.com/.

Electrical data - Ratings per IEC/EN

Ratings perIEC/EN 60664-1
Nominal voltage (III/3)250 V
Rated impulse withstand voltage (III / 3)4 kV
Rated current25 A
Legend (ratings)(III / 3) ≙ Overvoltage category III / Pollution degree 3
Ratings perIEC/EN 60664-1 / IEC/EN 60664-1 / IEC/EN 60664-1
Overvoltage categoryIII / III / II
Pollution degree3 / 2 / 2
Nominal voltage250 V
Rated impulse withstand voltage4 kV
Rated current25 A

Electrical data - Ratings per UL 1977

Note for the US marketSome versions may also be used for current interruption in accordance with the UL certificate in select applications with currents below 16 A and voltages up to 600 V. For further information, please contact your local sales office.
Rated voltage (UL 1977)600 V
Rated current UL 197723 A
Approvals perUL 1977
Rated voltage600 V
Rated current23 A

Electrical data - General information

Note on contact resistanceapprox. 1 mΩ of contact resistance approx. 0.25 mΩ contact transition plug/socket

Connection data

Total number of potentials3

Connection data - Connection 1

Pole number3

Physical data

Pin spacing10 mm / 0.394 inches
Width30 mm / 1.181 inches
Height32.7 mm / 1.287 inches
Depth45.8 mm / 1.803 inches

Mechanical data

UseControl technology
CodingB
Variable codingNo
Marking2/OUT 1/COM 2/IN
Potential marking2/OUT 1/COM 2/IN
Mating force of a plug-in connectionapprox. 20 … 70 N (depending on pole number)
Retention force of a plug-in connectionWhen locked: > 80 N
Unmating force of a plug-in connectionUnlocked: approx. 20 … 70 N (depending on pole number)
Number of mating cycles200, without resistive load
Type of distribution boxh-distribution connector for status queries
Protection typeIP20; When mated: IP2xC (These compact connectors are not designed for use in open, easily accessible areas!)

Plug-in connection

Contact type (pluggable connector)Socket/plug
Connector (connection type)for pluggable connectors
Mismating protectionYes
Note on mismating protectionAll WINSTA® components are 100% protected against mismating when:a.) plugging different numbers of polesb.) plugging while rotated 180 c.) plugging while laterally staggeredd.) plugging one pole
Locking leveryes
Locking of plug-in connectionlocking lever
Note on locking systemAll connectors for mounted installations (snap-in versions for lighting fixtures or devices, all types of PCB and distribution connectors) are factory-equipped with locking levers to ensure plugs and sockets are securely locked. Additional locking levers are only required for flying leads (plug/socket).
Number of locking levers3

Material data

Note (material data)Information on material specifications can be found here
Colorlight turquoise
Insulation material (main housing)Polyamide (PA66)
Flammability class per UL94V0
Contact materialCopper or copper alloy; surface-treated
Contact platingTin
Fire load0.335 MJ
Weight17.9 g

Environmental requirements

Processing temperature-5 … +40 °C
Continuous operating temperature-35 … +85 °C
Note on continuous operating temperatureInsulating parts for temperatures ≤ 105 °C

Commercial data

PU (SPU)25 pcs
Packaging typebox
Country of originDE
GTIN4055143767200
Customs tariff number85366990990

Product Classification

UNSPSC39121421
eCl@ss 10.027-44-06-03
eCl@ss 9.027-44-06-03
ETIM 9.0EC002567
ETIM 10.0EC002567
ECCNNO US CLASSIFICATION

Environmental Product Compliance

RoHS Compliance StatusCompliant,No Exemption