Fast delivery within 72 Hours

Wago 750-495/040-001

The 750-495 3-Phase Power Measurement Module measures electrical data in a three-phase supply network. The voltage is measured via network connection to L1, L2, L3 and N. The current of the three phas…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

The 750-495 3-Phase Power Measurement Module measures electrical data in a three-phase supply network. The voltage is measured via network connection to L1, L2, L3 and N. The current of the three phases is fed to I1, I2, I3 and IN (two clamping points each +,-) via current transformers or via Rogowski coils for the 750-495/000-002 Module. The module transmits metrics (e.g., reactive/apparent/effective power, energy consumption, power factor, phase angle, frequency, over-/undervoltage) directly into the process image, without requiring high computing power from the controller. Both comprehensive metrics and harmonic analysis up to the 41st harmonic permit extensive network analysis via the fieldbus. These metrics enable the operator to optimize supply to a drive or machine, protecting the system from damage and failure. Insulation failures can be detected and prevented via current measurement performed in the neutral conductor. The four-quadrant display indicates the load type (inductive, capacitive) and whether it is an energy consumer or producer.The device is ideal for operation in extreme environments thanks to:An extended temperature rangeHigher vibration and shock resistance

Specification

Technical data

Number of measurement inputs7 (3 voltage measurement inputs, 4 differential current measurement inputs)
Signal typePower measurement
Signal formSinusoidal signals (taking the cutoff frequency into account)
Resolution [bit]24 Bit
Data width2 x 128-bit data; 2 x 64-bit control/status
Voltage path input resistance (typ.)1429 kΩ
Current path input resistance (typ.)5 mΩ
Reference for measurement errorAC current/voltage
Measurement error (reference temperature)23 °C
Measurement error, deviation (max.) from the upper-range value0.5 %
Measurement current (max.)5 A
Measurement cycle timeAdjustable for the arithmetic mean value, min./max. values
Frequency range (mains frequency)50/60 Hz
Frequency range (harmonics analysis)0 … 3300 Hz
Limit frequency15.9 kHz
Permissible common mains supply systemsThree-phase, four-wire system: max. 277/480 VAC; Three-phase, three-wire system: max. 600 VAC (UL)
Note on common mains supply systemsULL up to 690°V is possible under special conditions (see manual).
Upper-range value for the measurement accuracy400/690 V
Calculated valuesLine-to-line voltage, power output, energy, power factors, mains frequency, harmonic analysis (up to the 41st harmonic), THD
Measurement methodTrue RMS measurement
Supply voltage (system)5 VDC; via data contacts
Current consumption (5 V system supply)100 mA
IndicatorsLED (A) green: Communication; LED (B-G) red: Error L1, Override in Current Measurement Path (display), Undervoltage in Voltage Measurement Path (display), Error L2, Error L3, Override in Voltage Measurement Path (display); LED (H) yellow: Interchange in Phase Sequence L1-L2-L3

Safety and protection

Measurement category per EN/UL 61010-2-030CAT III up to 3000 m; CAT II at 3000 m … 5000 m

Safety and protection - Test voltage

Test voltage3.51 kVAC, 50/60 Hz, 1 min.
Rated impulse withstand voltageSystem/field side: 5.0 kV (EN 60870-2-1 / Class VW3) 6.4 kV (EN/UL 61010-1)

Safety and protection - Insulation coordination per EN/UL 61010-2-201 with N connection

System voltage≤ 300 V
Note on system voltageThe system voltage corresponds to the line-to-neutral voltage derived from conventional mains power supply systems.
Overvoltage categoryIII up to 3000°m; II from 3000°m to 5000°m
Insulation typeReinforced insulation

Safety and protection - Insulation coordination per EN/UL 61010-2-201 without N connection

System voltage≤ 600 V
Note on system voltageTo ensure safe insulation, the module's N connector must not be connected. The system voltage corresponds to the line conductor/neutral conductor voltage, which was derived from standard power supply systems
Overvoltage categoryIII up to 3000°m; II from 3000°m to 5000°m
Insulation typeDouble isolation (basic isolation and supplementary isolation by impedance/current measurement transformer) Safe isolation from the adjacent SELV/PELV modules must be ensured. The product manual contains the types of isolation to adjacent modules in section “Isolation to Adjacent I/O Modules per EN/UL 61010 2-201.” Without double or reinforced isolation, the 750-495/040-00x Power Measurement Module must not be placed directly next to SELV/PELV modules. Under such conditions, the 750-616/040-000 Distance Module must be used.

Connection data

Connection technology: I/O12 x CAGE CLAMP®
Connectable conductor materialsCopper
Connection typeInputs/outputs
Solid conductor0.25 … 2.5 mm² / 24 … 14 AWG
Fine-stranded conductor0.25 … 2.5 mm² / 24 … 14 AWG
Strip length8 … 9 mm / 0.31 … 0.35 inches
Note (conductor cross-section)Solid conductor: 20 … 14 AWG (UL); Fine-stranded conductor: 20 … 16 AWG (UL) These values refer exclusively to the mechanical connection capacity of the clamping points. When the applications/devices are operated in locations covered by UL, only solid conductor with 20 … 14 AWG and fine-stranded conductor with 20 … 16 AWG are permitted.

Physical data

Width24 mm / 0.945 inches
Height100 mm / 3.937 inches
Depth67.8 mm / 2.669 inches
Depth from upper-edge of DIN-rail60.6 mm / 2.386 inches

Mechanical data

Mounting typeDIN-35 rail

Material data

Colordark gray
Housing materialPolycarbonate; polyamide 6.6
Fire load1.943 MJ
Weight91 g
Conformity markingCE

Environmental requirements

Ambient temperature (operation)-40 … +70 °C
Ambient temperature (storage)-40 … +85 °C
Ambient temperature (installation)-20 … +70 °C
Protection typeIP20
Pollution degree2 per EN 60664-1
Operating altitudewithout temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
Mounting positionHorizontal left, horizontal up, vertical top and vertical bottom
Relative humidity (without condensation)95 %
Relative humidity (with condensation)Short-term condensation per Class 3K7/IEC EN 60721-3-3 and E-DIN 40046-721-3 (except for wind-driven precipitation, water and ice formation)
Vibration resistanceAccording to type test for marine classification (ABS, BV, DNV, IACS, LR): acceleration: 5g, IEC 60068-2-6, EN 60870-2-2, IEC 60721-3-1, -3, EN 50155, EN 61373
Shock resistanceper IEC 60068-2-27 (10g/16 ms/half-sine/1,000 shocks; 25g/6 ms/half-sine/1,000 shocks), EN 50155, EN 61373
EMC immunity to interferenceper EN 61000-6-1, -2; EN 61131-2; marine applications; EN 50121-3-2; EN 50121-4, -5; EN 60255-26; EN 60870-2-1; EN 61850-3; IEC 61000-6-5; IEEE 1613; VDEW: 1994
EMC emission of interferenceper EN 61000-6-3, -4, EN 61131-2, EN 60255-26, marine applications, EN 60870-2-1, EN 61850-3, EN 50121-3-2, EN 50121-4, -5
Exposure to pollutantsper IEC 60068-2-42 and IEC 60068-2-43
Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %10 ppm
Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %25 ppm

Commercial data

PU (SPU)1 pcs
Packaging typeBox
Country of originDE
GTIN4055143353588
Customs tariff number85389099990

Product Classification

UNSPSC41113630
eCl@ss 10.027-24-26-05
eCl@ss 9.027-24-26-05
ETIM 9.0EC001596
ETIM 10.0EC001596
ECCNNO US CLASSIFICATION

Environmental Product Compliance

CAS-No.1303-86-2, 1317-36-8, 7439-92-1
REACH Candidate List SubstanceDiboron trioxide, Lead, Lead monoxide, Perfluorobutane sulfonic acid (PFBS) and its salts
RoHS Compliance StatusCompliant,With Exemption
RoHS Exemption6(c), 7(a), 7(c)-I, 7(c)-II
SCIP notification number (Austria)f08dcbf9-a12b-4273-8d9a-d673ea80b763
SCIP notification number (Belgium)49b5634e-8f95-472f-adeb-8d793c88fc4d
SCIP notification number (Bulgaria)6f012bbc-1755-4477-b55b-c17b20908162
SCIP notification number (Czech Republic)ab90c34e-7810-4765-8d01-859f978513b3
SCIP notification number (Denmark)7fb114f8-f780-4095-acb4-6b31912cc222
SCIP notification number (Finland)6e35119d-aefb-45af-8be4-e309a035d3cf
SCIP notification number (France)fb8f097b-afd2-4876-89ef-15487e6c3e80
SCIP notification number (Germany)b05d19ec-5b38-4136-a558-ee251cae62fb
SCIP notification number (Hungary)26c8b0ec-91f2-49a6-ac9e-a5f2810d1d2a
SCIP notification number (Italy)a51b136a-d213-4b08-a2eb-44ac3ac388cc
SCIP notification number (Netherlands)8914656e-1857-490e-9544-f95ea70faa90
SCIP notification number (Poland)eef617fd-f657-47b9-947b-b089d71d0710
SCIP notification number (Romania)9ca3b738-6799-4351-aa73-2056391c2255
SCIP notification number (Sweden)328f3a92-b7da-41eb-b078-4b2cb0778e24