B&R X67BC8513.L12-1
POWERLINK V1/V2Integrated hub for economical wiring12 digital channels, configurable as inputs or outputs1 analog input, 0 to 20 mA, 12-bitM8 connection typeI/O configuration and firmware update via t…
Shipping & Delivery
- 
Courier delivery
 
Our courier will deliver to the specified address
2-3 Days
From $20
- 
DHL Courier delivery
 
DHL courier will deliver to the specified address
2-3 Days
From $40
- 
Warranty 1 year
 
- 
Free 30-Day returns
 
Description
POWERLINK V1/V2Integrated hub for economical wiring12 digital channels, configurable as inputs or outputs1 analog input, 0 to 20 mA, 12-bitM8 connection typeI/O configuration and firmware update via the fieldbusIntegrated connection to the local expansion via X2X Link for up to 250 additional modulesConfigurable I/O cycle (starting at 200 µs)
The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler. Additional X2X Link I/O nodes (X67 modules or other modules based on X2X Link) can be connected using the integrated X2X Link connection. Mechanically, POWERLINK is connected via an IP67-rated standard D-coded M12 Ethernet connector.POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.
Specification
| Bus controller | 
 0x046C  | 
|---|---|
| Inputs/Outputs | 
 8x M12, A-coded  | 
| Insulation voltage between channel and bus | 
 500 Veff  | 
| Nominal voltage | 
 24 VDC  | 
| Internal I/O module | 
 0x04A8  | 
| Sensor/Actuator power supply | 
 Max. 12 W  | 
| Status indicators | 
 I/O function per channel, supply voltage, bus function  | 
| Outputs | 
 Yes, using LED status indicator and software  | 
| I/O power supply | 
 M8, 4-pin  | 
| Dynamic node allocation (DNA) | 
 Yes  | 
| Fieldbus | 
 200 μs  | 
| X2X Link | 
 250 μs  | 
| Power output | 
 15 W X2X Link power supply for I/O modules  | 
| Internal I/O | 
 0.6 W  | 
| X2X Link power supply | 
 17.25 W at maximum power output for connected I/O modules  | 
| CE | 
 Yes  | 
| UKCA | 
 Yes  | 
| CRA (Cyber Resilience Act) | 
 In preparation  | 
| Type | 
 Type 2  | 
| Variant | 
 Current-sourcing FET  | 
| Line length | 
 Max. 100 m between 2 stations (segment length)  | 
| Transfer rate | 
 100 Mbit/s  | 
| Physical layer | 
 100BASE-TX  | 
| Half-duplex | 
 Yes  | 
| Full-duplex | 
 No  | 
| Autonegotiation | 
 Yes  | 
| Auto-MDI/MDIX | 
 Yes  | 
| Hub propagation delay | 
 0.96 to 1 µs  | 
| Synchronization between bus systems possible | 
 Yes  | 
| Voltage range | 
 18 to 30 VDC  | 
| Integrated protective function | 
 Reverse polarity protection  | 
| Voltage | 
 I/O power supply minus voltage drop for short-circuit protection  | 
| Voltage drop for short-circuit protection at 0.5 A | 
 Max. 2 VDC  | 
| Summation current | 
 Max. 0.5 A  | 
| Short-circuit proof | 
 Yes  | 
| Input characteristics per EN 61131-2 | 
 Type 1  | 
| Input voltage | 
 18 to 30 VDC  | 
| Input current at 24 VDC | 
 Typ. 4 mA  | 
| Input circuit | 
 Sink  | 
| Input resistance | 
 Typ. 6 kΩ  | 
| Low | 
 <5 VDC  | 
| High | 
 >15 VDC  | 
| Signal form | 
 Square wave pulse  | 
| Counter size | 
 16-bit  | 
| Internal | 
 10 kHz  | 
| Pulse length | 
 >200 µs with 200 µs pause between pulses  | 
| Measurement type | 
 Propagation delay measurement between output and corresponding feedback input  | 
| Input | 
 0 to 20 mA  | 
| Input type | 
 Differential input  | 
| Digital converter resolution | 
 12-bit  | 
| Conversion time | 
 200 µs  | 
| Output format | 
 INT  | 
| Current | 
 0x0000 – 0x7FFF / 1 LSB = 0x0008 = 4.883 μA  | 
| Load | 
 <300 Ω  | 
| Input protection | 
 Protection against wiring with supply voltage  | 
| Permissible input signal | 
 Max. ±30 mA  | 
| Undershoot | 
 0x0000  | 
| Overshoot | 
 0x7FFF  | 
| Conversion procedure | 
 Successive approximation  | 
| Gain | 
 0.1%  | 
| Offset | 
 0.05%  | 
| Max. gain drift | 
 0.013 %/°C  | 
| Max. offset drift | 
 0.02 %/°C  | 
| DC | 
 >50 dB  | 
| 50 Hz | 
 >50 dB  | 
| Common-mode range | 
 ±2 V  | 
| Crosstalk between channels | 
 >70 dB  | 
| Nonlinearity | 
 <0.1%  | 
| Insulation voltage between input and bus | 
 500 Veff  | 
| Voltage drop at 20 mA | 
 Typ. 4.5 V  | 
| Cutoff frequency | 
 1 kHz  | 
| Slope | 
 40 dB  | 
| Switching voltage | 
 I/O power supply minus residual voltage  | 
| Nominal output current | 
 0.5 A  | 
| Total nominal current | 
 8 A  | 
| Output circuit | 
 Source  | 
| Output protection | 
 Thermal shutdown in the event of overcurrent or short circuit, integrated protection for switching inductive loads, reverse polarity protection of the output power supply  | 
| Diagnostic status | 
 Output monitoring with 10 ms delay  | 
| Leakage current when the output is switched off | 
 5 µA  | 
| Switching on after overload shutdown | 
 Approx. 10 ms (depends on the module temperature)  | 
| RDS(on) | 
 150 mΩ  | 
| Residual voltage | 
 <0.3 V at 0.5 A nominal current  | 
| Peak short-circuit current | 
 <12 A  | 
| 0 → 1 | 
 <400 µs  | 
| 1 → 0 | 
 <400 µs  | 
| Resistive load | 
 Max. 100 Hz  | 
| Inductive load | 
 See section "Switching inductive loads".  | 
| Braking voltage when switching off inductive loads | 
 50 VDC  | 
| Electrical isolation | 
 Bus isolated from POWERLINK and channel  | 
| Any | 
 Yes  | 
| 0 to 2000 m | 
 No limitation  | 
| >2000 m | 
 Reduction of ambient temperature by 0.5°C per 100 m  | 
| Degree of protection per EN 60529 | 
 IP67  | 
| Operation | 
 -25 to 60°C  | 
| Derating | 
 –  | 
| Storage | 
 -40 to 85°C  | 
| Transport | 
 -40 to 85°C  | 
| Width | 
 53 mm  | 
| Height | 
 155 mm  | 
| Depth | 
 42 mm  | 
| Weight | 
 360 g  | 
| M8 | 
 Max. 0.4 Nm  | 
| M12 | 
 Max. 0.6 Nm  | 
	
	
				
				
		
		
		
		
		
		
		
Reviews