Fast delivery within 72 Hours
B&R X67AI1223
4 analog inputs ±10 VOpen/Short circuit detectionConfigurable digital input filtersVery short cycle timesOptimal shield grounding on all channels
The modul…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
4 analog inputs ±10 VOpen/Short circuit detectionConfigurable digital input filtersVery short cycle timesOptimal shield grounding on all channels
The module is equipped with 4 inputs with 12-bit digital converter resolution. The range of the input signal is ±10 V.
Specification
| I/O module |
4 analog inputs ±10 V |
|---|---|
| B&R ID code |
0x16F1 |
| Status indicators |
I/O function per channel, supply voltage, bus function |
| Inputs |
4x M12, A-coded |
| I/O power supply |
M8, 4-pin |
| X2X Link |
M12, B-coded |
| Internal I/O |
3 W |
| X2X Link power supply |
0.75 W |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| KC |
Yes |
| Nominal voltage |
24 VDC |
| Voltage range |
18 to 30 VDC |
| Integrated protective function |
Reverse polarity protection |
| Sensor power supply |
Max. 12 W |
| Input |
±10 V |
| Input type |
Differential input |
| Digital converter resolution |
12-bit |
| Conversion time |
400 µs for all inputs |
| Output format |
INT |
| Voltage |
I/O power supply minus voltage drop for short-circuit protection |
| Input impedance in signal range |
20 MΩ |
| Input protection |
Protection against wiring with supply voltage |
| Permissible input signal |
Max. ±30 V |
| Undershoot |
0x8001 |
| Overshoot |
0x7FFF |
| Conversion procedure |
Successive approximation |
| Gain |
0.1% |
| Offset |
0.05% |
| Max. gain drift |
0.011%/°C |
| Max. offset drift |
0.009%/°C |
| DC |
>50 dB |
| 50 Hz |
>50 dB |
| Common-mode range |
±11 V |
| Crosstalk between channels |
<-70 dB |
| Nonlinearity |
<0.1% |
| Insulation voltage between input and bus |
500 Veff |
| Cutoff frequency |
1 kHz |
| Slope |
40 dB |
| Voltage drop for short-circuit protection at 500 mA |
Max. 2 VDC |
| Summation current |
Max. 0.5 A |
| Short-circuit proof |
Yes |
| Electrical isolation |
Channel isolated from bus Channel not isolated from channel |
| Any |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP67 |
| Operation |
-25 to 60°C |
| Derating |
– |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Width |
53 mm |
| Height |
85 mm |
| Depth |
42 mm |
| Weight |
200 g |
| M8 |
Max. 0.4 Nm |
| M12 |
Max. 0.6 Nm |

Reviews
Clear filtersThere are no reviews yet.