Fast delivery within 72 Hours

B&R X20SRT842

reACTION Technology module8 high-speed safe digital inputs, sink circuit4 pulse outputsSoftware input filter configurable for each channel4 safe digital outputs, output type A with 3 A, source circuit…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

reACTION Technology module8 high-speed safe digital inputs, sink circuit4 pulse outputsSoftware input filter configurable for each channel4 safe digital outputs, output type A with 3 A, source circuit2 high-speed safe digital outputs, output type B with 50 mA, source circuitSafe reACTION task cycle times starting at 150 µsIntegrated output protection

This reACTION Technology module is equipped with 8 high-speed safe digital inputs and 6 high-speed safe digital outputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read in digital signals and to control actuators in safety-related applications up to PL e or SIL 3.Ultrafast reACTION Technology makes it possible to control internal I/O channels with cycle times down to 150 µs. All commands that can be used for reACTION programs are available as function blocks in special libraries (e.g. AsIORTI). Programming in compliance with IEC 61131-3 requirements takes place in the Function Block Diagram editor in Automation Studio.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of switching cycles. The “high-side low-side” variant (output type A) is limited to actuators without reference potential (e.g. relays, valves). Type A outputs have safety-related advantages since the actuator can be cut off in its connection cable in all error scenarios. The “high-side high-side” variant (output type B) is required for actuators with reference potential (e.g. enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. The safe digital output modules are equipped with an error interlock in the event of network errors.This module is designed for X20 12-pin terminal blocks.

Specification

I/O module8 safe type A digital inputs, 4 pulse outputs, 24 VDC, 4 safe type A digital outputs, 24 VDC, 3 A, OSSD <500 µs, 2 safe type B2 digital outputs, 24 VDC, 50 mA, OSSD <500 µs, reACTION Technology
B&R ID code0xE7F7
Automation Studio4.2.5 or later
Automation Runtime4.2 or later
SafeDESIGNER4.2.2 or later
Safety Release1.10 or later
Mapp Technology Packagemapp Safety 5.7.0 or later
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
InputsYes, using LED status indicator and software
ReACTION-capable I/O channelsYes
ScopeModule
FunctionProgrammable
Standalone modeYes
Max. I/O cycle time800 µs
Bus0.4 W
Internal I/O2.5 W
Safe digital HS-LS outputs0.84
Safe digital HS-HS outputs0.175
Pulse outputs0.8
Channel - BusYes
Channel - ChannelNo
Type of signal linesShielded lines must be used for all signal lines.
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 GcIP20, Ta (see X20 user’s manual)FTZÚ 09 ATEX 0083X
ULcULus E115267Industrial control equipment
Mission timeMax. 20 years
OpenSAFETY wiredNegligible
OpenSAFETY wireless<1*10-14 * Number of openSAFETY packets per hour
Proof test interval (PT)20 years
CategoryCat. 3 if parameter “Disable OSSD = Yes – Warning”, Cat. 4 if parameter “Disable OSSD = No”
PLPL d if parameter “Disable OSSD = Yes – Warning”, PL e if parameter “Disable OSSD = No”
DC>60% if parameter “Disable OSSD = Yes – Warning”, >94% if parameter “Disable OSSD = No”
MTTFD per channel100 years if parameter “Disable OSSD = Yes – Warning”, 2500 years if parameter “Disable OSSD = No”
SIL CLSIL 2 if parameter “Disable OSSD = Yes – Warning”, SIL 3 if parameter “Disable OSSD = No”
SFF>60% if parameter “Disable OSSD = Yes – Warning”, >90% if parameter “Disable OSSD = No”
PFH / PFHd per channel<5*10-8 if parameter "Disable OSSD = Yes - Warning", <1*10-10 if parameter "Disable OSSD = No"
PFD per channel<1*10-3 if parameter "Disable OSSD = Yes - Warning", <2*10-5 if parameter "Disable OSSD = No"
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Quantity4
VariantPush-Pull
Input characteristics per EN 61131-2Type 1
Hardware≤130 µs
SoftwareConfigurable between 0 and 500 ms
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 3.28 mA
Input resistanceMin. 7.33 kΩ
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Low<5 VDC
High>15 VDC
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded lineMax. 400 m with shielded line
Nominal output current50 mA
Total nominal current200 mA
Output protectionShutdown of individual channels in the event of overload or short circuit
Braking voltage when switching off inductive loadsMax. 45 VDC
Error detection1 s
Peak short-circuit current0.5 A for 120 µs
Leakage current when the output is switched off0.1 mA
RDS(on)80 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section “Inrush current behavior for output channels”.
Test pulse lengthMax. 500 µs
Max. capacitive load100 nF
IOUT<100 µA
IGND<50 mA
Short-circuit current15 mAeff
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 2x safety-keyed terminal block separately.Order 1x safety-keyed bus module separately.
Pitch25+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20SRT842”