Fast delivery within 72 Hours

B&R X20SO2110

2 safe digital outputs with 0.5 ASource circuitOutput type ACurrent monitoringOpen circuit detectionIntegrated output protection

This module is equipped wi…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 safe digital outputs with 0.5 ASource circuitOutput type ACurrent monitoringOpen circuit detectionIntegrated output protection

This module is equipped with 2 safe digital outputs. The nominal output current is 0.5 A.The module can be used for controlling actuators in safety-related applications up to PL e or SIL 3.The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The “high-side low-side” variant (output type A) is limited to actuators without reference potential (e.g. relays, valves). Type A outputs have safety-related advantages since the actuator can be cut off in its connection cable in all error scenarios. Safe digital output channels provide protection against automatic restart when network errors occur and also using a current measurement for open circuit detection.This module is designed for X20 12-pin terminal blocks.

Specification

I/O module2 safe type A digital outputs, with current monitoring, 24 VDC, 0.5 A, OSSD <500 µs
B&R ID code0x1F16
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time800 µs
Bus0.25 W
Internal I/O0.98 W
Additional power dissipation caused by actuators (resistive) [W]0.12
Channel - BusYes
Channel - ChannelNo
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC21B Temperature: 5 – 45°C Vibration: 0.7 g EMC: Bridge and open deck
KCYes
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Quantity2
VariantFET, 1x positive switching, 1x negative switching, type A, output level readable, open-circuit detection
Nominal output current0.5 A
Total nominal current1 A
Output protectionSee section “Inrush current behavior for output channels”.
Braking voltage when switching off inductive loadsMax. 90 VDC
Open-circuit detectionVia internal current measurement, output current 50 mA: Signal “CurrentOK” = TRUE
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section “Inrush current behavior for output channels”.
Leakage current when the output is switched off<10 µA
RDS(on)240 mΩ
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section “Inrush current behavior for output channels”.
Test pulse lengthMax. 500 µs
Time between two test pulsesMin. 49.5 ms
Max. capacitive load100 nF
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
Pitch25+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20SO2110”