Fast delivery within 72 Hours

B&R X20SI4110

 740,94

3 in stock

4 safe digital inputs4 pulse outputsSink circuitSoftware input filter configurable for each channelSingle-width module

This single-width module is equipped…

3 in stock

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 safe digital inputs4 pulse outputsSink circuitSoftware input filter configurable for each channelSingle-width module

This single-width module is equipped with 4 safe digital inputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read various digital signals in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.This module is designed for X20 12-pin terminal blocks.

Specification

I/O module4 safe type A digital inputs, 4 pulse outputs, 24 VDC
B&R ID code0x2D13
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time1 ms
Bus0.4 W
Internal I/O2.5 W
Additional power dissipation caused by actuators (resistive) [W]0.8
Channel - BusYes
Channel - ChannelNo
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyIEC 61508:2010, SIL 3 EN 62061:2005/A2:2015, SIL 3 EN ISO 13849-1:2015, Cat. 4 / PL e IEC 61511:2004, SIL 3
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module (single-width) separately.
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Quantity4
VariantPush-Pull
Input characteristics per EN 61131-2Type 1
Hardware≤150 μs
SoftwareConfigurable between 0 and 500 ms
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 3.28 mA
Input resistanceMin. 7.33 kΩ
Error detection time100 ms
Insulation voltage between channel and bus500 Veff
Low<5 VDC
High>15 VDC
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded line Max. 400 m with shielded line
Nominal output current50 mA
Output protectionShutdown of individual channels in the event of overload or short circuit
Peak short-circuit current0.5 A for 120 µs
Short-circuit current15 mAeff
Leakage current when the output is switched off0.1 mA
RDS(on)80 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Total nominal current200 mA
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20SI4110”