Fast delivery within 72 Hours

B&R X20SC2432

2 safe digital inputs, sink circuit2 pulse outputsSoftware input filter configurable for each channel2 safe relay outputsOutput type “Relay”Relay module for 48 VAC / 24 VDCSwitching current 6 ANormall…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 safe digital inputs, sink circuit2 pulse outputsSoftware input filter configurable for each channel2 safe relay outputsOutput type “Relay”Relay module for 48 VAC / 24 VDCSwitching current 6 ANormally open contactSingle-channel isolated outputs

The module is equipped with 2 safe digital inputs and 2 safe relay outputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read digital signals and for floating control of actuators in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.Safety relays are installed in the module. The positively driven feedback contacts are evaluated internally by the module. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.

Specification

I/O module2 safe type A digital inputs, 2 pulse outputs, 24 VDC, 2 relays with 1 normally open contact each, 48 VAC / 6 A, 24 VDC / 6 A
B&R ID code0xA7A4
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
InputsYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time1 ms
Bus0.26 W
Internal I/O1.15 W
Relay outputs1.44
Pulse outputs0.1
Channel - BusYes
Channel - ChannelYes
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: A (0 to 45°C) Humidity: B (up to 100%) Vibration: A (0.7 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC21B Temperature: 5 – 45°C Vibration: 0.7 g EMC: Bridge and open deck
KCYes
EN 50155Yes
EN 61810-3Yes
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Quantity2
VariantPush-Pull
Input characteristics per EN 61131-2Type 1
Hardware≤150 μs
SoftwareConfigurable between 0 and 500 ms
Input circuitSink
Input voltage24 VDC -15% / +20%
Input current at 24 VDCMin. 2 mA to max. 4.59 mA
Input resistanceMin. 5.23 kΩ
Error detection time100 ms
Insulation voltage between channel and busSafe disconnection of 300 VAC per EN 50178
Low<5 VDC
High>15 VDC
Line length between signal source (pulse output or external signal) and inputMax. 60 m with unshielded line Max. 400 m with shielded line
Nominal output current50 mA
Diagnostic statusContact position determined by positively driven contacts
Max. switching frequencySee section “Inrush current behavior for output channels”.
0 → 1<50 ms
1 → 0<50 ms
Insulation voltage between channel and channel48 VAC
Contact resistance (without terminal block)20 mΩ
Contact service lifeSee “Contact service life”.
Short-circuit/Overload protectionExternal 6 A gL/gG fuse (melting fuse), LS automat C characteristic 1.6 A
Switching voltage range5 to 24 VDC, 5 to 48 VAC
Coil voltage24 VDC -15% / +20%
Short-circuit proofYes, 1000 A (with specified short-circuit/overload protection)
Max. inrush current30 A for 20 ms
Overvoltage category per EN 60664-1II
AC148 VAC / 6 A
AC1548 VAC / 3 A
DC124 VDC / 6 A
DC1324 VDC / 5 A / 0.1 Hz
UL 508B300 / R300
Output protectionShutdown of individual channels in the event of overload or short circuit
Peak short-circuit current25 A for 5 ms
Short-circuit current1.4 Aeff
Leakage current when the output is switched off0.1 mA
RDS(on)20 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Total nominal current100 mA
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
Pitch25+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20SC2432”

Your email address will not be published. Required fields are marked *