Description
4 digital outputsControls external power triacs or non-parallel thyristorsOutputs with 48 – 240 VAC50 Hz or 60 HzOutputs electrically isolated from one anotherPhase-angle controlZero-crossing detectionNegative half-waves can be switched off2-wire connections240 V codingOSP modeFrequency mode
The module is a digital output module that is equipped with 4 opto-triac outputs using phase-angle control. L and N are fed to the module for zero-crossing detection.The 4 outputs are electrically isolated from one another and are used for controlling external power triacs or nonparallel thyristors.
Specification
| I/O module | 4 digital outputs for controlling external power triacs or non-parallel thyristors |
|---|---|
| B&R ID code | 0xAD05 |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Outputs | Yes, using LED status indicator |
| Bus | 0.8 W |
| Internal I/O | – |
| External I/O | – |
| Additional power dissipation caused by actuators (resistive) [W] | +1 W |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| KC | Yes |
| Variant | Opto-triac |
| Circuit | Normally open contact |
| Nominal voltage | 48 to 240 VAC |
| Max. voltage | 264 VAC |
| Rated frequency | 47 to 63 Hz |
| Nominal output current | 80 mA |
| Total nominal current | 320 mA |
| Output current | 50 mA |
| Summation current | 200 mA |
| Connection type | 2-wire connections |
| Zero-crossing detection | Yes |
| Holding current | Max. 3.5 mA |
| Leakage current | Max. 1.5 mA (per channel) |
| Residual voltage (on-state voltage) | Max. 3 V |
| Area | 5 to 95% |
| Resolution | 1% |
| Accuracy (60 to 240 VAC) | <100 μs |
| Voltage monitoring L - N | No |
| Recommended wiring | Twisted pair cabling to the terminal pairs |
| Line length | Max. 10 m |
| Overvoltage protection between L and N | Yes |
| Channel - Bus | Tested at 2300 VAC |
| Channel - Channel | Tested at 2300 VAC |
| External | Generally fuse |
| Internal | Snubber circuit (RC element) and varistor |
| Electrical isolation | Channel isolated from channel, bus and I/O power supply |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Not permitted |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | – |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB32 separately. Order 1x bus module X20BM12 separately. |
| Pitch | 12.5+0.2 mm |