Fast delivery within 72 Hours
B&R X20DC2398
2 SSI absolute encoder 24 V2 additional inputs24 VDC and GND for encoder supply
This module is equipped with two inputs for SSI absolute encoders with 24 V…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
2 SSI absolute encoder 24 V2 additional inputs24 VDC and GND for encoder supply
This module is equipped with two inputs for SSI absolute encoders with 24 V encoder signal.
Specification
| I/O module |
2 SSI absolute encoder 24 V |
|---|---|
| Input voltage |
24 VDC -15% / +20% |
| B&R ID code |
0x1BAD |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Bus |
0.01 W |
| Internal I/O |
1.4 W |
| Additional power dissipation caused by actuators (resistive) [W] |
– |
| Type of signal lines |
Shielded lines must be used for all signal lines. |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| DNV |
Temperature: B (0 to 55°C) |
| CCS |
Yes |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC33B |
| KC |
Yes |
| Quantity |
2 |
| Nominal voltage |
24 VDC |
| Input characteristics per EN 61131-2 |
Type 1 |
| Input current at 24 VDC |
Approx. 3.3 mA |
| Input circuit |
Sink |
| Hardware |
≤2 µs |
| Software |
– |
| Connection type |
3-wire connections |
| Input resistance |
7.19 kΩ |
| Low |
<5 VDC |
| High |
>15 VDC |
| Insulation voltage between channel and bus |
500 Veff |
| Encoder inputs |
24 V, asymmetrical |
| Counter size |
32-bit |
| Max. transfer rate |
125 kbit/s |
| Encoder power supply |
Module-internal, max. 600 mA |
| Coding |
Gray/Binary |
| CLK: Output current |
Max. 100 mA |
| DATA: Input resistance |
18.4 kΩ |
| Insulation voltage between encoder and bus |
500 Veff |
| Overload characteristics of encoder power supply |
Short-circuit proof, overload-proof |
| Electrical isolation |
Bus isolated from encoder and channel Channel not isolated from channel and encoder Encoder not isolated from encoder |
| Horizontal |
Yes |
| Vertical |
Yes |
| 0 to 2000 m |
No limitation |
| >2000 m |
Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
– |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
5 to 95%, non-condensing |
| Note |
Order 1x terminal block X20TB12 separately. |
| Pitch |
12.5+0.2 mm |

Reviews