Fast delivery within 72 Hours

B&R X20cSO6300

6 safe digital outputs with 0.2 ASource circuitOutput type BIntegrated output protection

This module is equipped with 6 safe digital outputs. The nominal o…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

6 safe digital outputs with 0.2 ASource circuitOutput type BIntegrated output protection

This module is equipped with 6 safe digital outputs. The nominal output current is 0.2 A.The module can be used for controlling actuators in safety-related applications up to PL e or SIL 3.The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The “high-side high-side” variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.

Specification

I/O module6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs
B&R ID code0xDD88
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time1 ms
Bus0.32 W
Internal I/O1.4 W
Additional power dissipation caused by actuators (resistive) [W]1.128
Channel - BusYes
Channel - ChannelNo
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
NoteOrder 1x safety-keyed terminal block separately. Order 1x safety-keyed bus module separately.
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protective functionReverse polarity protection
Quantity6
VariantFET, 2x positive switching, type B1, output level readable
Nominal output current0.2 A
Total nominal current1.2 A
Output protectionSee section “Inrush current behavior for output channels”.
Braking voltage when switching off inductive loadsMax. 45 VDC
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section “Inrush current behavior for output channels”.
Leakage current when the output is switched off<100 µA
RDS(on)4.7 Ω
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section “Inrush current behavior for output channels”.
Test pulse lengthMax. 10 µs
Max. capacitive load100 nF
IOUT<100 µA
IGND<70 mA
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
DeratingSee section “Derating”.
Starting temperatureYes, -25°C
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
OperationUp to 100%, condensing
Pitch25+0.2 mm