Fast delivery within 72 Hours
B&R X20cSC2212
6 safe digital inputs, sink circuit6 pulse outputsSoftware input filter configurable for each channel2 safe digital outputs, output type B with 0.5 A, source circuitIntegrated output protection…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
6 safe digital inputs, sink circuit6 pulse outputsSoftware input filter configurable for each channel2 safe digital outputs, output type B with 0.5 A, source circuitIntegrated output protection
The module is equipped with 6 safe digital inputs and 2 safe digital outputs. It is designed for a nominal voltage of 24 VDC.The module can be used to read in digital signals and to control actuators in safety-related applications up to PL e or SIL 3.The module is equipped with filters that are individually configurable for switch-on and switch-off behavior. The module also provides pulse signals for diagnosing the sensor line.The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The “high-side high-side” variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.This module is designed for X20 12-pin terminal blocks.
Specification
| I/O module |
6 safe type A digital inputs, 6 pulse outputs, 24 VDC, 2 safe type B1 digital outputs, 24 VDC, 0.5 A, OSSD <500 µs |
|---|---|
| B&R ID code |
0xDD9D |
| Status indicators |
I/O function per channel, operating state, module status |
| Module run/error |
Yes, using LED status indicator and software |
| Outputs |
Yes, using LED status indicator and software |
| Inputs |
Yes, using LED status indicator and software |
| Scope |
Module |
| Function |
Module functionality |
| Standalone mode |
No |
| Max. I/O cycle time |
1 ms |
| Bus |
0.25 W |
| Internal I/O |
1.4 W |
| Safe digital outputs |
0.075 |
| Pulse outputs |
0.264 |
| Channel - Bus |
Yes |
| Channel - Channel |
No |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
In preparation |
| Functional safety |
EN 50156-1:2004 |
| ATEX |
Zone 2, II 3G Ex nA nC IIA T5 Gc |
| UL |
cULus E115267 |
| HazLoc |
cCSAus 244665 |
| DNV |
Temperature: A (0 to 45°C) |
| LR |
ENV1 |
| KR |
Yes |
| ABS |
Yes |
| BV |
EC21B |
| Note |
Order 1x safety-keyed terminal block separately. |
| Nominal voltage |
24 VDC |
| Voltage range |
24 VDC -15% / +20% |
| Integrated protective function |
Reverse polarity protection |
| Quantity |
6 |
| Variant |
Push-Pull |
| Input characteristics per EN 61131-2 |
Type 1 |
| Hardware |
≤150 μs |
| Software |
Configurable between 0 and 500 ms |
| Input circuit |
Sink |
| Input voltage |
24 VDC -15% / +20% |
| Input current at 24 VDC |
Min. 2 mA to max. 3.28 mA |
| Input resistance |
Min. 7.33 kΩ |
| Error detection time |
1 s |
| Insulation voltage between channel and bus |
500 Veff |
| Low |
<5 VDC |
| High |
>15 VDC |
| Line length between signal source (pulse output or external signal) and input |
Max. 60 m with unshielded line |
| Nominal output current |
20 mA |
| Total nominal current |
120 mA |
| Output protection |
Shutdown of individual channels in the event of overload or short circuit |
| Braking voltage when switching off inductive loads |
Max. 45 VDC |
| Peak short-circuit current |
25 A for 15 µs |
| Leakage current when the output is switched off |
0.1 mA |
| RDS(on) |
110 Ω |
| Switching voltage |
I/O power supply minus voltage drop due to RDS(on) |
| Max. switching frequency |
See section "Inrush current behavior for output channels". |
| Test pulse length |
Max. 500 µs |
| Max. capacitive load |
100 nF |
| IOUT |
<1 mA |
| IGND |
<180 mA |
| Short-circuit current |
100 mAeff |
| Horizontal |
Yes |
| Vertical |
Yes |
| Installation elevation above sea level |
0 to 2000 m, no limitation |
| Degree of protection per EN 60529 |
IP20 |
| Horizontal mounting orientation |
-25 to 60°C |
| Vertical mounting orientation |
-25 to 50°C |
| Derating |
See section "Derating". |
| Starting temperature |
Yes, -40°C |
| Storage |
5 to 95%, non-condensing |
| Transport |
5 to 95%, non-condensing |
| Operation |
Up to 100%, condensing |
| Pitch |
25+0.2 mm |

Reviews
Clear filtersThere are no reviews yet.