B&R X20cPD2113

Integrated exchangeable microfuseMonitoring of the fusePotential for routing as neededCan be used as feed module for the I/O supply

The potential distribut…

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

2-3 Days

From $20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From $40

  • Warranty 1 year
  • Free 30-Day returns

Description

Integrated exchangeable microfuseMonitoring of the fusePotential for routing as neededCan be used as feed module for the I/O supply

The potential distributor module with feed can provide 6x 24 VDC and 6x ground connections from the internal I/O supply on the terminals. This module can also be used instead of a special feed module for the internal I/O supply. The internal 24 VDC supply is connected to the terminal connections through a replaceable microfuse for protection. The 24 VDC feed and the functionality of the fuse are monitored.

Specification

Potential distributor module with supply

6x 24 VDC on the terminals, 6x ground on the terminals

B&R ID code

0xE23B

Status indicators

Operating state, module status

Module run/error

Yes, using LED status indicator and software

Fuse monitoring

Yes, using LED status indicator and software

Bus

0.12 W

Internal I/O

1.15 W

External I/O

1.15 W

Additional power dissipation caused by actuators (resistive) [W]

CE

Yes

UKCA

Yes

ATEX

Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X

UL

cULus E115267
Industrial control equipment

HazLoc

cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5

DNV

Temperature: B (0 to 55°C)
Humidity: B (up to 100%)
Vibration: B (4 g)
EMC: B (bridge and open deck)

LR

ENV1

KR

Yes

ABS

Yes

BV

EC33B
Temperature: 5 – 55°C
Vibration: 4 g
EMC: Bridge and open deck

Nominal input voltage

24 VDC -15% / +20% external, ground external

Input current

Max. 6 A

Fuse

Integrated 6.3 A, slow-blow, can be replaced

Behavior on short circuit

No protection available
Use an external fuse.

Reverse polarity protection

No

Nominal output voltage

24 VDC, ground

Permissible contact load

6 A

On 24 VDC power supply

Integrated fuse

On GND power supply

No protection available

Horizontal

Yes

Vertical

Yes

0 to 2000 m

No limitation

>2000 m

Reduction of ambient temperature by 0.5°C per 100 m

Degree of protection per EN 60529

IP20

Horizontal mounting orientation

-25 to 60°C

Vertical mounting orientation

-25 to 50°C

Derating

Storage

5 to 95%, non-condensing

Transport

5 to 95%, non-condensing

Operation

Up to 100%, condensing

Note

Order 1x terminal block X20TB12 separately.
Order 1x bus module X20cBM01 or X20cBM11 separately.

Pitch

12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20cPD2113”

Your email address will not be published. Required fields are marked *