B&R X20CMR011

Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesSaving user data directly on the moduleSupports blac…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Measurement and evaluation of the ambient conditions in the control cabinetRecording ambient conditionsRecording operating hours and power-on cyclesSaving user data directly on the moduleSupports blackout mode2 inputs for PT1000 temperature sensors2 digital inputs 24 VDC1 digital output 24 VDC

The module is designed for measuring ambient conditions in the control cabinet as well as recording operating hours and power-on cycles. In addition, the module offers the option of storing user data directly on the module, is equipped with inputs/outputs and supports blackout mode.Measuring and evaluating ambient conditionsThe ambient conditions are continuously evaluated by the module. The duration in which individual parameters are within certain ranges is stored internally. This makes it possible, for example, to determine how long the system remained in a certain temperature range. The histograms recorded by the module can be read out by the user.Internal module memory for user dataWith 512 kB nonvolatile user memory (flash), data from the application can be saved directly on the module and also read back from the module. The data is therefore retained after the module or CPU is restarted and remains with the module in the event that the module is connected to another machine or system, for example. Data retention is maintenance-free – without batteries.Inputs/OutputsThe module is equipped with 2 inputs for Pt1000 temperature sensors, 2 digital inputs (24 VDC) and 1 digital output (24 VDC).Blackout modeThe integrated blackout mode ensures that module functionality is maintained even in the event of network failure.

Specification

I/O moduleMeasurement of ambient conditions: Temperature in the module, relative humidity, vibration, shock, position, operating hours, power-on cycles 2 digital inputs, 1 digital output, 2 PT1000 temperature inputs
B&R ID code0x28B4
Status indicatorsI/O function by channel, overload, memory access, operating state, module status
Module run/errorYes, using LED status indicator and software
OutputYes, using LED status indicator and software (output error status)
ScopeModule
FunctionModule functionality
Standalone modeNo
Bus0.4 W
Internal I/O0.1 W
Additional power dissipation caused by actuators (resistive) [W]+0.075
Type512 kB flash memory
Sectors8 sectors, 64 kB each
Data retention20 years at 55°C
Guaranteed erase/write cycles100,000 per sector
Error-correcting code (ECC)No
Write protectionNo
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
Quantity1
Nominal voltage24 VDC
Input voltage24 VDC -15% / +20%
Input current at 24 VDCTyp. 3.75 mA
Input circuitSink
Hardware≤100 μs
SoftwareDefault 1 ms, configurable between 0 and 25 ms in 0.2 ms increments
Connection type1- or 2-wire connections
Input resistanceTyp. 6.4 kΩ
Low<5 VDC
High>15 VDC
Insulation voltage between channel and bus500 Veff
InputResistance measurement for 2-wire connections
Digital converter resolution12-bit
Filter timeConfigurable
Conversion time1 ms for all inputs
Output formatINT
Pt10001 LSB = 0.1°C
Input filterAveraging with clipping function
Linearization methodInternal
Permissible input signalShort-term ±15 V
Max. gain drift0.0003 %/°C
Max. offset drift0.06 %/°C
Nonlinearity<0.010%
Range undershoot0x8001
Range overshoot0x7FFF
Open circuit0x7FFF
General fault0x8000
Open inputs0x7FFF
Sensor positionModule-internal
Sampling rateTyp. 10 ms
Measurement range±2000 dps
Resolution±70 mdps per LSB
Max. error±2% at 10 to 80% relative humidity ±3% at 80% relative humidity
Linearity over temperature±1.5% at -40 to 85°C
Offset calibration error±10 dps
VariantCurrent-sourcing FET
Switching voltage24 VDC -15% / +20%
Nominal output current0.5 A
Output circuitSource
Diagnostic statusOutput monitoring with 10 ms delay
Leakage current when the output is switched off120 µA
RDS(on)300 mΩ
0 → 1<300 µs
1 → 0<300 µs
Resistive loadMax. 100 Hz
Inductive loadSee section “Switching inductive loads”.
Short-circuit proofYes
Overload-proofTemporary overload
Electrical isolationAnalog channel not isolated from bus Digital channel isolated from bus Digital channel not isolated from digital channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm