Fast delivery within 72 Hours
B&R X20cDOF322
16 digital outputsSource connection1-wire connectionsIntegrated output protection
The module is equipped with 16 outputs for 1-wire connections. The module…
Shipping & Delivery
- 
Courier delivery
 
Our courier will deliver to the specified address
2-3 Days
From $20
- 
DHL Courier delivery
 
DHL courier will deliver to the specified address
2-3 Days
From $40
- 
Warranty 1 year
 
- 
Free 30-Day returns
 
Description
16 digital outputsSource connection1-wire connectionsIntegrated output protection
The module is equipped with 16 outputs for 1-wire connections. The module is designed for source output wiring.
Specification
| I/O module | 
 16 digital outputs 24 VDC for 1-wire connections  | 
|---|---|
| B&R ID code | 
 0xDD4C  | 
| Status indicators | 
 I/O function per channel, operating state, module status  | 
| Module run/error | 
 Yes, using LED status indicator and software  | 
| Outputs | 
 Yes, using LED status indicator and software (output error status)  | 
| Bus | 
 0.28 W  | 
| Internal I/O | 
 0.95 W  | 
| Additional power dissipation caused by actuators (resistive) [W] | 
 +0.56  | 
| CE | 
 Yes  | 
| UKCA | 
 Yes  | 
| CRA (Cyber Resilience Act) | 
 In preparation  | 
| ATEX | 
 Zone 2, II 3G Ex nA nC IIA T5 Gc  | 
| UL | 
 cULus E115267  | 
| HazLoc | 
 cCSAus 244665  | 
| DNV | 
 Temperature: B (0 to 55°C)  | 
| LR | 
 ENV1  | 
| KR | 
 Yes  | 
| ABS | 
 Yes  | 
| BV | 
 EC33B  | 
| Variant | 
 Current-sourcing FET  | 
| Nominal voltage | 
 24 VDC  | 
| Switching voltage | 
 24 VDC -15% / +20%  | 
| Nominal output current | 
 0.5 A  | 
| Total nominal current | 
 8 A  | 
| Connection type | 
 1-wire connections  | 
| Output circuit | 
 Source  | 
| Output protection | 
 Thermal shutdown in the event of overcurrent or short circuit (see value "Short-circuit peak current")  | 
| Diagnostic status | 
 Output monitoring with 10 ms delay  | 
| Leakage current when the output is switched off | 
 5 µA  | 
| RDS(on) | 
 140 mΩ  | 
| Peak short-circuit current | 
 <3 A  | 
| Switch-on in the event of overload shutdown or short-circuit shutdown | 
 Approx. 10 ms (depends on the module temperature)  | 
| 0 → 1 | 
 <300 µs  | 
| 1 → 0 | 
 <300 µs  | 
| Resistive load | 
 Max. 500 Hz  | 
| Inductive load | 
 See section "Switching inductive loads".  | 
| Braking voltage when switching off inductive loads | 
 Typ. 45 VDC  | 
| Insulation voltage between channel and bus | 
 500 Veff  | 
| Electrical isolation | 
 Channel isolated from bus  | 
| Horizontal | 
 Yes  | 
| Vertical | 
 Yes  | 
| 0 to 2000 m | 
 No limitation  | 
| >2000 m | 
 Reduction of ambient temperature by 0.5°C per 100 m  | 
| Degree of protection per EN 60529 | 
 IP20  | 
| Horizontal mounting orientation | 
 -25 to 60°C  | 
| Vertical mounting orientation | 
 -25 to 50°C  | 
| Derating | 
 See section "Derating".  | 
| Storage | 
 5 to 95%, non-condensing  | 
| Transport | 
 5 to 95%, non-condensing  | 
| Operation | 
 Up to 100%, condensing  | 
| Note | 
 Order 1x terminal block X20TB1F separately.  | 
| Pitch | 
 12.5+0.2 mm  | 
	
	
				
				
		
		
		
		
		
		
		
Reviews