Fast delivery within 72 Hours

B&R X20cAI1744

1 full-bridge strain gauge inputData output rate configurable from 0.1 Hz to 7.5 kHzSpecial operating modes (synchronous mode and multiple sampling)Configurable filter level…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

1 full-bridge strain gauge inputData output rate configurable from 0.1 Hz to 7.5 kHzSpecial operating modes (synchronous mode and multiple sampling)Configurable filter level

This module works with both 4-wire and 6-wire strain gauge load cells. The concept applied by the module requires compensation in the measurement system. This compensation eliminates the absolute uncertainty in the measurement circuit, such as component tolerances, effective bridge voltage or zero point offset. The measurement precision refers to the absolute (compensated) value, which will only change as a result of changes in the operating temperature.

Specification

I/O module1 full-bridge strain gauge input
B&R ID code0xE754
Status indicatorsChannel status, operating state, module status
Module run/errorYes, using LED status indicator and software
Open circuitYes, using LED status indicator and software
InputYes, using LED status indicator and software
Bus0.01 W
Internal I/O0.5 W
Additional power dissipation caused by actuators (resistive) [W]Max. +0.36
CEYes
UKCAYes
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
Strain gauge factor2 to 256 mV/V, configurable using software
Connection4- or 6-wire connections
Input typeDifferential, used to evaluate a full-bridge strain gauge
Digital converter resolution24-bit
Conversion timeDepends on the configured data output rate
Data output rate0.1 – 7500 samples per second, configurable using software (fDATA)
Cutoff frequency5 kHz
Order3
Slope60 dB
ADC filter characteristicsSigma-delta, see section “Filter characteristics of the sigma-delta A/D converter”
Operating range / Measurement sensor85 to 5000 Ω
Influence of cable lengthSee section “Calculation example”.
Input protectionRC protection
Common-mode range0 to 3 VDC Permissible input voltage range (with regard to the electric potential strain gauge GND) on inputs “Input +” and “Input -“
Insulation voltage between input and bus500 Veff
Conversion procedureSigma-delta
Broken bridge supply lineValue approaching 0
Broken sensor lineValue approaching ±end value (status bit “Line monitoring” is set in register “Module status”)
Valid range of values0xFF800001 to 0x007FFFFF (-8,388,607 to 8,388,607)
Voltage5.5 VDC / Max. 65 mA
Short-circuit and overload-proofYes
Voltage drop for short-circuit protectionMax. 0.2 VDC at 65 mA and 25°C
2 mV/V1.31 nV
4 mV/V2.62 nV
8 mV/V5.25 nV
16 mV/V10.49 nV
32 mV/V20.98 nV
64 mV/V41.96 nV
128 mV/V83.92 nV
256 mV/V167.85 nV
Max. gain drift12 ppm/°C
Max. offset drift2 ppm/°C
Nonlinearity<10 ppm
Electrical isolationBus isolated from analog input and strain gauge supply voltage Channel not isolated from I/O power supply
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
DeratingSee section “Hardware configuration”
Starting temperatureYes, -40°C
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
OperationUp to 100%, condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20cBM11 separately.
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20cAI1744”

Your email address will not be published. Required fields are marked *