Fast delivery within 72 Hours

B&R X20ATC402

6 channels for thermocouplesFor sensor types J, K, N, S, B, R, E, C, T, raw value measurementIntegrated terminal temperature compensation2x PT1000 sensor integrated in the terminal (X20TB1E)2x externa…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

6 channels for thermocouplesFor sensor types J, K, N, S, B, R, E, C, T, raw value measurementIntegrated terminal temperature compensation2x PT1000 sensor integrated in the terminal (X20TB1E)2x external PT1000 sensor can be connected (X20TB1F)Configurable filter timeConfigurable resolutionNetTime timestamp: Moment of measurement

The module is equipped with 6 inputs for J, K, N, S, B, R, E, C and T thermocouple sensors.This module can also be equipped with the X20TB1E thermocouple terminal block with integrated PT1000 temperature sensors. This makes it possible to achieve optimal terminal temperature compensation.

Specification

I/O module6 inputs for thermocouples
B&R ID code0xBB99
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Bus0.01 W
Internal I/O0.85 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
KCYes
InputThermocouple
Digital converter resolution16-bit
Filter timeConfigurable between 1 and 200 ms
N channels(n + 2) * 4 * x ms
1 channelx ms
Output formatINT
Type J: Fe-CuNi±0.0033 %/°C
Type K: NiCr-Ni±0.0042 %/°C
Type N: NiCrSi-NiSi±0.0048 %/°C
Type S: PtRh10-Pt±0.0123 %/°C
Type B: PtRh30-PtRh6±0.0166 %/°C
Type R: PtRh13-Pt±0.0109 %/°C
Type E: NiCr-CuNi±0.003 %/°C
Type C: WRe5-WRe26±0.0062 %/°C
Type T: Cu-CuNi±0.011%/°C
Terminal temperature±0.004%
Voltage±0.003 %/°C
Sensor standardEN 60584
Sensor temperature1 LSB = 0.1°C or 0.01°C
Range undershoot0x8001 or 0x80000001
Range overshoot0x7FFF or 0x7FFFFFFF
Open circuit0x7FFF or 0x7FFFFFFF
Open inputs0x7FFF or 0x7FFFFFFF
General fault0x8000 or 0x80000000
Conversion procedureSigma-delta
Linearization methodInternal
Permissible input signalMax. ±15 V
Input filterFirst-order low-pass filter / cutoff frequency 500 Hz
Gain±0.04%
Channel±0.004%
Operating modesInternal/remote or external
With natural convection±1.5°C after 20 min
With artificial convection±3°C after 20 min
DC>100 dB
50 Hz>100 dB
60 Hz>100 dB
Common-mode range±14 V
Crosstalk between channels<-70 dB
Between channel and bus500 Veff
Electrical isolationChannel isolated from bus Channel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB1E for internal/remote terminal temperature compensation separately. Order 1x terminal block X20TB1F for external terminal temperature compensation separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20ATC402”

Your email address will not be published. Required fields are marked *