Fast delivery within 72 Hours
B&R X20AO2632-1
2 analog outputsEither current or voltage signal possibleExtended signal range16-bit digital converter resolutionNetTime timestamp: Switch-off time
The mod…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
2 analog outputsEither current or voltage signal possibleExtended signal range16-bit digital converter resolutionNetTime timestamp: Switch-off time
The module is equipped with 2 outputs with 16-bit (including sign) digital converter resolution. It is possible to select between the current and voltage signal using different terminals. This module is designed for X20 6-pin terminal blocks. If needed (e.g. for logistical reasons), the 12-pin terminal block can also be used.
Specification
| I/O module | 2 analog outputs ±11 V or 0 to 22 mA |
|---|---|
| B&R ID code | 0xC36E |
| Status indicators | I/O function per channel, operating state, module status |
| Module run/error | Yes, using LED status indicator and software |
| Channel type | Yes, using software |
| Bus | 0.01 W |
| Internal I/O | 1.25 W |
| Additional power dissipation caused by actuators (resistive) [W] | – |
| CE | Yes |
| UKCA | Yes |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| DNV | Temperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck) |
| CCS | Yes |
| LR | ENV1 |
| KR | Yes |
| ABS | Yes |
| BV | EC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck |
| KC | Yes |
| Output | ±11 V or 0 to 22 mA, via different terminal connections |
| Voltage | Max. 0.1%, from 10 MΩ → 1 kΩ, resistive |
| Current | Max. 0.5%, from 1 Ω → 600 Ω, resistive |
| Conversion time | 50 µs for all outputs |
| Settling time on output change over entire range | 500 µs |
| Switch on/off behavior | Internal enable relay for startup |
| Gain | 0.08% |
| Offset | 0.05% |
| Output protection | Short-circuit proof |
| Short-circuit proof | Current limiting ±40 mA |
| Output filter | First-order low-pass filter / cutoff frequency 10 kHz |
| Nonlinearity | <0.007% |
| Insulation voltage between channel and bus | 500 Veff |
| Electrical isolation | Channel isolated from bus Channel not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | – |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB06 or X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2 mm |

Reviews