B&R X20AI4636

4 analog inputsCurrent or voltage signal configuration for the entire module16-bit digital converter resolutionMinimum conversion time of 40 µs for all inputsThe conversion time for the entire module…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

4 analog inputsCurrent or voltage signal configuration for the entire module16-bit digital converter resolutionMinimum conversion time of 40 µs for all inputsThe conversion time for the entire module can be configured in 0.02 µs steps.Maximum 14 samples (16-bit) for the entire module per X2X Link cycleOversampling: Up to 16 analog values per channel (internal)Timestamp for the last conversion of an X2X Link cycle

The module is equipped with 4 inputs with 16-bit digital converter resolution. It is possible to select between the current and voltage signal using different terminals. With the oversampling function, up to 16 analog values per channel can be recorded.

Specification

I/O module4 analog inputs ±10 V or 0 to 20 mA
B&R ID code0xB3A8
Status indicatorsI/O function per channel, operating state, module status
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Channel typeYes, using software
Bus0.01 W
Internal I/O1.5 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
KCYes
Input±10 V or 0 to 20 mA, via different terminal connections
Input typeDifferential input
Voltage<0.01%
Current<0.015%
Conversion time40 μs for all inputs
Output formatINT
Input protectionProtection against wiring with supply voltage
Conversion procedureSAR
Input filterHardware – Third-order low-pass filter / cutoff frequency 10 kHz
Gain0.08%
Offset0.02%
DC70 dB
50 Hz70 dB
Common-mode range±12 V
Crosstalk between channels<-70 dB
Insulation voltage between channel and bus500 Veff
Electrical isolationChannel isolated from bus Channel not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
DeratingSee section “Derating”.
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20AI4636”

Your email address will not be published. Required fields are marked *