Fast delivery within 72 Hours

B&R X20AI2437

2 analog current measurement inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionNetTime timestamp: Moment of measurement…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

2 analog current measurement inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionNetTime timestamp: Moment of measurement

The module is equipped with 2 current measurement inputs with 16-bit digital converter resolution.Each current measurement input has its own sensor supply. The two channels with their respective sensor supplies are electrically isolated from each other. The user can select between the two measurement ranges 4 to 20 mA and 0 to 25 mA.

Specification

I/O module2 analog inputs 4 to 20 mA or 0 to 25 mA
B&R ID code0xB784
Status indicatorsI/O function per channel, operating state, module status, sensor power supply per channel
Module run/errorYes, using LED status indicator and software
InputsYes, using LED status indicator and software
Sensor power supplyYes, using LED status indicator and software
Bus0.05 W
Internal I/O1.15 W
Additional power dissipation caused by actuators (resistive) [W]
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X
ULcULus E115267 Industrial control equipment
HazLoccCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5
DNVTemperature: B (0 to 55°C) Humidity: B (up to 100%) Vibration: B (4 g) EMC: B (bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC33B Temperature: 5 – 55°C Vibration: 4 g EMC: Bridge and open deck
KCYes
Input4 to 20 mA or 0 to 25 mA configurable using software
Input typeDifferential input
Digital converter resolution16-bit
Data output rate4.7 to 960 samples per second, configurable using software
Output formatINT
4 to 20 mA0.0007 %/°C
0 to 25 mA0.0002 %/°C
0 to 25000 µAINT 0x0000 – 0x61A8 / 1 LSB = 0x0001 = 1000 nA
LoadI_IN ≥ 0.1 mA: R < 8000 Ω I_IN ≥ 1 mA: R < 1100 Ω I_IN ≥ 4 mA: R < 510 Ω
Input protectionUp to 30 VDC, reverse polarity protection (max. 0.1 A)
Open-circuit detectionYes, using software
Permissible input signal0 to 25 mA
Output of digital value during overloadConfigurable
Conversion procedureSigma-delta
DC80 dB
50 HzDepends on the sampling rate: e.g. >130 dB for 50 samples per second
Common-mode range0 to 7 V
Nonlinearity<0.003%
HardwareFirst-order low-pass filter / cutoff frequency 2.5 kHz
SoftwareSinc4 filter
Channel - Channel1000 VAC
Channel - Bus1000 VAC
Channel - Ground1000 VAC
Power consumption0.75 W per channel
Nominal voltage25 V ±2%
Nominal output currentMax. 30 mA
Short-circuit proofYes, continuous
Up to 100 kHz≤2.2 mV
Up to 1 MHz≤22 mV
Higher≤100 mV
Typical<50 mA
Maximum60 mA
Behavior on short circuitCurrent limiting
Electrical isolationChannel isolated from channel and bus Sensor power supply isolated from sensor power supply Sensor power supply not isolated from channel
HorizontalYes
VerticalYes
0 to 2000 mNo limitation
>2000 mReduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529IP20
Horizontal mounting orientation-25 to 60°C
Vertical mounting orientation-25 to 50°C
Derating
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Operation5 to 95%, non-condensing
NoteOrder 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately.
Pitch12.5+0.2 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R X20AI2437”

Your email address will not be published. Required fields are marked *