Fast delivery within 72 Hours
B&R X20AI2237
2 analog voltage inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionVery high sampling rateNetTime timestamp: Moment of measurement…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
2 analog voltage inputsElectrically isolated analog channelsElectrically isolated sensor supplies16-bit digital converter resolutionVery high sampling rateNetTime timestamp: Moment of measurement
The module is equipped with 2 voltage measurement inputs with 16-bit digital converter resolution.Each voltage input has its own sensor supply. The two channels with their respective sensor supplies are electrically isolated from each other.
Specification
| I/O module | 2 analog inputs ±10 V |
|---|---|
| B&R ID code | 0xC9C4 |
| Status indicators | I/O function per channel, operating state, module status, sensor power supply per channel |
| Module run/error | Yes, using LED status indicator and software |
| Inputs | Yes, using LED status indicator and software |
| Sensor power supply | Yes, using LED status indicator and software |
| Bus | 0.05 W |
| Internal I/O | 1.05 W (Rev. ≥D0), 1.15 W (Rev. <D0) |
| Additional power dissipation caused by actuators (resistive) [W] | – |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | In preparation |
| ATEX | Zone 2, II 3G Ex nA nC IIA T5 Gc IP20, Ta (see X20 user’s manual) FTZÚ 09 ATEX 0083X |
| UL | cULus E115267 Industrial control equipment |
| HazLoc | cCSAus 244665 Process control equipment for hazardous locations Class I, Division 2, Groups ABCD, T5 |
| Input | ±10 V |
| Input type | Differential input |
| Digital converter resolution | ±15-bit |
| Data output rate | 10000 samples per second |
| Data type | INT |
| Voltage | INT 0x8001 – 0x7FFF / 1 LSB = 0x0001 = 305.176 µV |
| Input impedance in signal range | 20 MΩ |
| Input protection | Up to 30 VDC, reverse polarity protection |
| Open-circuit detection | Yes, using software |
| Permissible input signal | Max. ±30 V |
| Output of digital value during overload | Configurable |
| Conversion procedure | SAR |
| Input filter | Fourth-order low-pass filter / Cutoff frequency 10 kHz |
| Gain | 0.013% |
| Offset | 0.0035% |
| Max. gain drift | <0.0008%/°C |
| Max. offset drift | <0.0025%/°C |
| DC | 84 dB |
| Up to 60 Hz | 84 dB |
| Up to 10 kHz | 82 dB |
| Common-mode range | ±14 V |
| Nonlinearity | <0.003% |
| Channel - Channel | 1000 VAC |
| Channel - Bus | 1000 VAC |
| Channel - Ground | 1000 VAC |
| Bus - Ground | 800 VAC |
| Power consumption | 0.75 W per channel |
| Nominal voltage | 25 V ±2% |
| Nominal output current | Max. 30 mA |
| Short-circuit proof | Yes, continuous |
| Up to 100 kHz | ≤2.2 mV |
| Up to 1 MHz | ≤22 mV |
| Higher | ≤100 mV |
| Typical | <50 mA |
| Maximum | 60 mA |
| Behavior on short circuit | Current limiting |
| Electrical isolation | Channel isolated from channel and bus Sensor power supply isolated from sensor power supply Sensor power supply not isolated from channel |
| Horizontal | Yes |
| Vertical | Yes |
| 0 to 2000 m | No limitation |
| >2000 m | Reduction of ambient temperature by 0.5°C per 100 m |
| Degree of protection per EN 60529 | IP20 |
| Horizontal mounting orientation | -25 to 60°C |
| Vertical mounting orientation | -25 to 50°C |
| Derating | – |
| Storage | 5 to 95%, non-condensing |
| Transport | 5 to 95%, non-condensing |
| Operation | 5 to 95%, non-condensing |
| Note | Order 1x terminal block X20TB12 separately. Order 1x bus module X20BM11 separately. |
| Pitch | 12.5+0.2 mm |