Description

Connection for temperature sensorOptimally suited for ACOPOSmulti 8BVP power supply modules

ACOPOSmulti regeneration choke, 90 A, 480 V, terminal blocks

Specification

Cooling and mounting typeWall mounting
CEYes
UKCAYes
ULcULus E225616 Power conversion equipment
KCYes
Mains input voltage3x 220 to 3x 480 VAC ±10%
Frequency50 / 60 Hz ±4%
Allocation to power supply module8BVP0880HC00.00x-1 8BVP0880HW00.00x-1
Continuous current90 Aeff
Peak current <10 s180 Aeff
Face-up mounting orientation0.6 Aeff per °C (starting at 10°C)
Vertical mounting orientation1 Aeff per °C (starting at 40°C)
Starting at 1000 m above sea level7.2 Aeff per 1,000 m
Power dissipation at nominal current420 W
U1, V1, W1Terminals
U2, V2, W2Terminals
On mainsNo
On deviceNo
Solid core / Multiple-conductor lines2.5 to 50 mm²
With wire end sleeve0.5 to 2.5 mm²
UL/C-UL-US30 to 12 AWG
CSA26 to 12 AWG
Inductance0.5 mH
T+, T-Terminals
Hanging verticallyNo
Horizontal, face upYes
Standing horizontallyYes
Nominal5 to 40°C
Maximum55°C
Pollution degree per EN 61800-5-12 (non-conductive pollution)
Overvoltage category per EN 61800-5-1III
Degree of protection per EN 60529IP20
Storage5 to 95%
TransportMax. 95% at 40°C
Operation5 to 85%
Width293 mm
Height412 mm
Depth165 mm
Weight40.2 kg