Fast delivery within 72 Hours

B&R 8B0C0320HC00.00A-1

Input for connecting an external 24 VDC source (e.g. UPS)Connections for supplying external 24 V devicesExtensive protective measures

ACO…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Input for connecting an external 24 VDC source (e.g. UPS)Connections for supplying external 24 V devicesExtensive protective measures

ACOPOSmulti auxiliary supply module, 32 A, AS, cold plate or pass-through mounting, 24 VIn 1x 30 A, 24 VOut 1x 30 A, 1x 5 A

Specification

Cooling and mounting typeCold plate or pass-through mounting
CEYes
UKCAYes
CRA (Cyber Resilience Act)In preparation
ULcULus E225616 Power conversion equipment
KCYes
Nominal5 to 40°C
Operating range in continuous operation260 to 800 VDC
Full continuous power315 to 800 VDC
Continuous power consumptionMax. 880 W
Power dissipation with continuous power22 W (0% continuous power) 35 W (50% continuous power) 80 W (100% continuous power)
DC bus capacitance220 nF
VariantConnector
Continuous power800 W
DC bus voltage (UDC): 260 to 315 VDC25 VDC * (UDC / 315)
DC bus voltage (UDC): 315 to 800 VDC24 VDC ±6%
Normal mode (via DC bus)32 ADC
Supply mode (via +24 Vin)30 ADC
Reduction of continuous power at ambient temperatures starting at 40°CNo reduction
Starting at 500 m above sea level80 W per 1000 m
Reduction of continuous power depending on cooling methodNo reduction
Startup delayMax. 1 s
Startup timeApprox. 5 to 20 ms
Residual rippleTyp. 50 mVSS
Output voltage25 VDC ±1.6%
DC bus voltage (UDC): 350 to 800 VDC42 ADC
No-load proofYes
Overload-proofYes, ticker operation on overload (TON = 1 s,TOFF = 2.4 s)
Short-circuit proofYes
Feedback protectionMax. 35 VDC (also when the power is switched off)
Overtemperature protectionYes
Dielectric strength to ground±50 VDC
Output/Input isolationSELV / PELV requirements
Protection of 24 VDC Out 1 output30 A (slow-blow) electronic, automatic reset
Protection of 24 VDC Out 2 output5 A (slow-blow) electronic, automatic reset
24 VDC, COMConnector
With wire end sleeve0.25 to 2.5 mm²
UL/C-UL-US22 to 10 AWG
CSA22 to 10 AWG
CircuitSink
Input - 24 VDCYes
Modulation compared to ground potentialMax. ±50 V
Maximum55°C
Low (24 VDC Out 1 is switched on)<5 V
High (24 VDC Out 1 is switched off)>15 V
Input current at nominal voltageApprox. 10 mA
ON (24 VDC Out 1 is switched on)Max. 25 ms
OFF (24 VDC Out 1 is switched off)Max. 0.25 ms
Minimum23 VDC
Voltage drop between input and internal 24 VDC system power supply<0.5 V
Switch-on threshold+24 VDC internal system power supply <21.5 VDC
Max. continuous current30 A
When switching to supply modeTyp. 5 ms
When starting up via 24 VinTyp. 2 s
Status indicators24Vi LED ERRi LED
Undervoltage detectionYes (<20 VDC)
Overvoltage detectionYes (>26 VDC)
24 VDC In, COMConnector
With wire end sleeves0.5 to 6 mm²
Hanging verticallyYes
Horizontal, face upYes
Standing horizontallyNo
Pollution degree per EN 61800-5-12 (non-conductive pollution)
Overvoltage category per EN 61800-5-1III
Degree of protection per EN 60529IP20
Storage5 to 95%
TransportMax. 95% at 40°C
Operation5 to 85%
Width53 mm
Height317 mm
Cold plate212 mm
Pass-through mounting209 mm
WeightApprox. 2.9 kg
Module width1

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “B&R 8B0C0320HC00.00A-1”

Your email address will not be published. Required fields are marked *