Fast delivery within 72 Hours
B&R 4PP015.C420-36
Power Panel, 24 VDC, 153 x 120 mm, LCD display, 4 x 20 characters, Cyrillic, backlight, 26 keys, 300 kB SRAM, 1024 kB FlashPROM, 1 RS232, 1 CAN interface network-capable, 8 digital inputs, 24 VDC, sin…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Power Panel, 24 VDC, 153 x 120 mm, LCD display, 4 x 20 characters, Cyrillic, backlight, 26 keys, 300 kB SRAM, 1024 kB FlashPROM, 1 RS232, 1 CAN interface network-capable, 8 digital inputs, 24 VDC, sink/source, 2 event counters or 1 incremental encoder or 2x gate/period measurement, 8 digital outputs, 24 VDC, 0.5 A source, 4 analog inputs, ±10 V, 12-bit, two of the analog inputs can be used as KTY10 or Pt1000 inputs, 4 analog outputs, ±10 V, 12-bit, IP65 protection (front), order 2x TB718, 1x TB103 terminal blocks separately!
Specification
| Type | CAN |
|---|---|
| Variant | 9-pin male DSUB connector |
| Status indicators | I/O function per channel, status |
| I/O function | Yes, using LEDs |
| Interface | Yes, using LEDs |
| State | Yes, using LED status indicator |
| CE | Yes |
| UKCA | Yes |
| CRA (Cyber Resilience Act) | Evaluation ongoing |
| UL | cULus E115267 Industrial control equipment |
| Voltage monitoring | An NMI is triggered at a supply voltage of <15 VDC. |
| System bus for expansions | No |
| Typical instruction cycle time | 0.8 µs |
| Watchdog | Yes |
| Accuracy | Resolution 1 s |
| System PROM | 448 kB FlashPROM |
| User PROM | 1024 kB FlashPROM |
| User RAM | 300 kB SRAM |
| Resolution | 4 x 20 characters |
| Display character set | English/Cyrillic |
| Electrical isolation | Yes |
| Max. baud rate | 115.2 kbit/s |
| Max. distance | 1000 m |
| Bus length ≤60 m | 500 kbit/s |
| Bus length ≤200 m | 250 kbit/s |
| Bus length ≤1000 m | 50 kbit/s |
| Quantity | 4 |
| Nominal voltage | 24 VDC |
| Input circuit | IEC 61131-2 |
| Channel 1-3 | Counters |
| Channel 4-16 | – |
| Group isolation | No |
| Channel - Bus | Yes |
| Channel - Channel | No |
| Input | Resistance measurement in 2-wire method with constant current supply |
| Digital converter resolution | 12-bit |
| Conversion time | 150 µs for all channels |
| Output format | INT |
| Input impedance in signal range | 20 MΩ |
| Hardware | Cutoff frequency 10 kHz / slope 60 dB |
| Software | – |
| Resistance measurement range | 0-4000 Ω |
| Note | Configurable per channel |
| KTY10-6 | -50 to 125°C |
| Pt1000 | -200 to 850°C |
| Nominal output current | 0.5 A |
| Total nominal current | 4 A |
| Output circuit | Source |
| Output protection | Single-channel continuous short circuit protection |
| Internal protective circuit | VDR |
| Output | ±10 V |
| Switch on/off behavior | Internal enable relay for startup and errors |
| Basic accuracy | ±0.088% at 25°C based on the current output value |
| Function keys | 10 with LED (yellow) |
| Soft keys | No |
| System keys | Numeric keys, cursor block |
| Power consumption | Max. 6 W |
| Degree of protection per EN 60529 | IP65 (front) |
| Operation | 10 to 90% |
| Storage | 5 to 95% |
| Width | 153 mm |
| Height | 120 mm |
| Depth | 46.1 mm |
| Weight | 0.5 kg |

Reviews