Fast delivery within 72 Hours
B&R 0PS1200.3
Minimum space requirement in the control cabinet due to a thin designRobust and reliable thanks to dynamic boost with a strong output characteristic curve for starting heavy loadsOptical and preventiv…
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
2-3 Days
From $20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From $40
-
Warranty 1 year
-
Free 30-Day returns
Description
Minimum space requirement in the control cabinet due to a thin designRobust and reliable thanks to dynamic boost with a strong output characteristic curve for starting heavy loadsOptical and preventive function monitoring with three-color LED and dry switching contactEasy handling due to push-in connections, label fields, wire stripping mark and tamper-resistant setupCan be connected in parallel for increased power and redundancyTemperature range: -25°C to +70°CWorldwide use thanks to AC and DC wide-range inputInternational certification package
24 VDC power supply unit, 1-phase, 20 A, input 100 to 240 VAC, wide range, thin design, top-hat rail installation
Specification
| Status display |
Green LED (DC OK), threshold value Uout > 21 V |
|---|---|
| Input - Output |
3 kV DC (type test) |
| Input - Ground |
1.5 kV DC (type test) |
| Input - Signal |
3 kV DC (type test) |
| Active DC OK switch output |
See section "Dry switching contact". |
| Connection type |
Push-in connection |
| CE |
Yes |
| UKCA |
Yes |
| CRA (Cyber Resilience Act) |
Not applicable |
| UL |
cULus E534663 |
| DNV |
Temperature: D (-25 to 55°C) |
| Nominal input voltage |
100 to 240 VAC |
| Input voltage |
100 to 240 VAC -15% to +10% |
| Network type |
Star network (TN, TT, IT(PE)) |
| Frequency |
50 to 60 Hz ±10% |
| Inrush current |
<21 A |
| Current consumption |
5.3 A / 2.15 A (100 VAC / 240 VAC) |
| I2t |
<1.091 A2s |
| Power failure bypass |
Typ. 23 ms (120 VAC) |
| Leakage current to PE |
<3.5 mA |
| Protective circuit |
Varistor transient protection |
| Internal fuse |
10 A |
| Required line fuse for device and line protection |
See section "Input protection". |
| Nominal voltage |
24 VDC |
| Output power |
480 W / Max. 720 W (5 s) |
| Output voltage |
24 to 28 VDC |
| Output current |
20 A / Max. 30 A (5 s) |
| Setting range for output voltage |
24 to 28 VDC |
| Control deviation |
<0.1% (input voltage change ±10%) |
| Rise time |
≤1 s (UOUT (10 to 90%)) |
| Residual ripple |
Typ. 50 mVSS |
| Can be connected in parallel |
Yes, for increased efficiency and redundancy |
| Can be connected in series |
Yes, for increased output voltage (observe SELV limit) |
| Overvoltage protection |
≤35 VDC (on the output (OVP)) |
| Protective functions |
Short-circuit protection |
| Feedback voltage resistance |
≤35 VDC |
| Efficiency |
Typ. 93.49% (120 VAC) |
| MTBF |
230 VAC / >1,400,000 h (25°C) |
| Rated load |
<33.37 W (120 VAC) |
| No-load operation |
<1.3 W (120 VAC) |
| Horizontal |
Yes |
| Vertical |
No |
| Maximum |
5000 m |
| Flammability class |
V0 |
| Ventilation/Cooling |
Normal convection, no fan required |
| Degree of protection per EN 60529 |
IP20 |
| Protection class |
I |
| Operation |
18 ms, 30 g, in each direction, per IEC 60068-2-27 |
| Derating |
See section "Derating". |
| Starting temperature |
-40°C |
| Storage |
-40 to 85°C |
| Transport |
-40 to 85°C |
| Pollution degree |
2 |
| Climate category |
3K3, per EN 60721 |
| Overvoltage category |
III (≤2000 m) / II (≤5000 m), per EN 61010-1 |
| Material |
Aluminum sheet, plastic cover PA |
| Coating |
No protective coating |
| Installation |
Easy top-hat rail installation (NS 35 rails, EN 60715) |
| Width |
55 mm |
| Height |
135 mm |
| Depth |
132 mm |
| Weight |
940 g |

Reviews