Fast delivery within 72 Hours

IFM PN4227

PN4227

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Potential-free Triac output for currents up to 2.5 A
For use in AC power mains
Country-specific pressure units selectable
Clearly visible 4-digit LED display
With long-term stability thanks to high overload protection

Specification

Product characteristics

Number of inputs and outputsNumber of digital outputs: 1
Measuring range0...1 bar
0...1000 mbar
0...14.5 psi
0...100 kPa
0...1 bar0...1000 mbar
Process connectionthreaded connection 1/4" NPT internal thread

Application

Applicationfor industrial applications
Medialiquids and gases
Medium temperature[°C] [°C]-25...80
Min. burst pressure30000 mbar
430 psi
3000 kPa
30000 mbar430 psi
Pressure rating10000 mbar
145 psi
1000 kPa
10000 mbar145 psi
Type of pressurerelative pressure

Electrical data

Operating voltage tolerance[%] [%]5...10
Operating voltage[V] [V]90...250 AC
Nominal voltage AC[V] [V]< 250
Current consumption[mA] [mA]< 10
Min. insulation resistance[MΩ] [MΩ]100; (500 V DC)
Protection classII
Reverse polarity protectionno
Power-on delay time[s] [s]0.2
Integrated watchdogyes

Inputs / outputs

Number of inputs and outputsNumber of digital outputs: 1

Outputs

Total number of outputs1
Output signalswitching signal
Electrical designTriac
Number of digital outputs1
Output functionnormally open / normally closed; (parameterisable)
Max. voltage drop switching output AC[V] [V]2
Permanent current rating of switching output AC[mA] [mA]250; ((...70 °C) 1000 (...60 °C) 1500 (...45 °C) 2500 (...20 °C))
Switching frequency AC[Hz] [Hz]< 160
Short-circuit proofno
Overload protectionno

Measuring/setting range

Measuring range0...1 bar
0...1000 mbar
0...14.5 psi
0...100 kPa
0...1 bar0...1000 mbar
Set point SP10...999 mbar
0.1...14.6 psi
1...99.9 kPa
10...999 mbar0.1...14.6 psi
Reset point rP5...994 mbar
0.1...14.5 psi
0.5...99.4 kPa
5...994 mbar0.1...14.5 psi
In steps of1 mbar
0.1 psi
0.1 kPa
1 mbar0.1 psi

Accuracy / deviations

Switch point accuracy[% of the span] [% of the span]< ± 1,0
Repeatability[% of the span] [% of the span]< ± 0,1; (with temperature fluctuations < 10 K)
Linearity deviation[% of the span] [% of the span]< ± 0,5
Hysteresis deviation[% of the span] [% of the span]< ± 0,1
Long-term stability[% of the span] [% of the span]< ± 0,1; (per year)
Temperature coefficient zero point[% of the span / 10 K] [% of the span / 10 K]< ± 0,2; (-25...80 °C)
Temperature coefficient span[% of the span / 10 K] [% of the span / 10 K]< ± 0,3; (-25...80 °C)

Response times

Delay time programmable dS, dr[s] [s]0, 0,2,...10, 11,...50
Damping process value dAP[s] [s]0...4

Software / programming

Adjustment of the switch pointprogramming button
Parameter setting optionshysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit

Operating conditions

Ambient temperature[°C] [°C]-25...80
Storage temperature[°C] [°C]-40...100
ProtectionIP 65

Tests / approvals

EMCEN 61000-4-2 ESD
4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated
10 V/m
EN 61000-4-4 Burst
2 kV
EN 61000-4-6 HF conducted
10 V
EN 61000-4-2 ESD4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated10 V/m
EN 61000-4-4 Burst2 kV
EN 61000-4-6 HF conducted10 V
Shock resistanceDIN IEC 68-2-27
50 g (11 ms)
DIN IEC 68-2-2750 g (11 ms)
Vibration resistanceDIN IEC 68-2-6
20 g (10...2000 Hz)
DIN IEC 68-2-620 g (10...2000 Hz)
MTTF[years] [years]224.58
Pressure Equipment DirectiveSound engineering practice; can be used for group 2 fluids; group 1 fluids on request

Mechanical data

Weight[g] [g]356.65
Housingcylindrical
Dimensions[mm] [mm]Ø 34 / L = 120
Materialsstainless steel (304/1.4301); PC; PBT; PA; FKM
Materials (wetted parts)stainless steel (303/1.4305); ceramics; FKM
Min. pressure cycles100 million
Process connectionthreaded connection 1/4" NPT internal thread
Restrictor element integratedno (can be retrofitted)

Displays / operating elements

Displayswitching status
LED, red
function display
7-segment LED display
measured values
7-segment LED display
switching statusLED, red
function display7-segment LED display
measured values7-segment LED display

Electrical connection

Required protectionminiature fuse to IEC60127-2 sheet 1; ≤ 5 A; fast acting

Remarks

Remarksn.c. = not used
Pack quantity1 pcs.

Electrical connection

Connector1 x 1/2"; coding: C

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “IFM PN4227”

Your email address will not be published. Required fields are marked *