Fast delivery within 72 Hours
IFM AC6000
AC6000
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Reliable transmission of machine data, process parameters and diagnostic data to the controller
Simple replacement of units due to integrated parameter memory
Robust housing for use in harsh industrial environments
For connection of up to four IO-Link devices
Specification
Application
| Application | field installation |
|---|---|
| Daisy-chain function | power supply; fieldbus interface |
Electrical data
| Operating voltage[V] [V] | 18...31.6 DC; (AS-i) |
|---|---|
| Current consumption[mA] [mA] | 300...1500; (AUX) |
| Max. current consumption from AS-i[mA] [mA] | 100 |
| Protection class | III |
| Max. current load total[A] [A] | 1.1; (ports 1+2: 0,55 (AUX); ports 3+4: 0,55 (AUX)) |
| Additional voltage supply[V] [V] | 20...30 DC; (AUX) |
Inputs / outputs
| Total number of inputs and outputs | 8; (configurable) |
|---|---|
| Number of inputs and outputs | Number of digital inputs: 8; Number of digital outputs: 4 |
Inputs
| Number of digital inputs | 8; (IO-Link Port Class A: 4 x 2) |
|---|---|
| Sensor supply of the inputs | AUX |
| Switching level high[V] [V] | 11...30 |
| Switching level low[V] [V] | 0...5 |
| Digital inputs protected against short circuits | yes |
Outputs
| Number of digital outputs | 4; (IO-Link Port Class A: 4 x 1) |
|---|---|
| Max. current load per output[mA] [mA] | 300 |
| Short-circuit proof | yes |
| Actuator supply outputs | AUX |
Interfaces
| Communication interface | IO-Link; AS-i |
|---|---|
| Transmission type | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
| IO-Link revision | 1.1 |
| Number of ports class A | 4 |
Operating conditions
| Ambient temperature[°C] [°C] | -25...60 |
|---|---|
| Storage temperature[°C] [°C] | -25...85 |
| Max. relative air humidity[%] [%] | 90 |
| Protection | IP 65; IP 66; IP 67 |
| Protection rating (NEMA 250) | 6P |
| Pollution degree | 2 |
| Chemical media | ISO 16750-5 AA, BA, BD, HLP, CC, DB, DC, DD, CA NEMA 250 5.13.1 AA |
| ISO 16750-5 | AA, BA, BD, HLP, CC, DB, DC, DD, CA |
| NEMA 250 5.13.1 | AA |
Tests / approvals
| EMC | EN 61000-6-2 EN 61000-6-4 |
|---|---|
| Shock resistance | DIN EN 60068-2-27 |
| Vibration resistance | DIN EN 60068-2-64 2009-04 DIN EN 60068-2-6 2008-10 |
| MTTF[years] [years] | 161 |
AS-i classification
| AS-i version | 2.11; 3.0 |
|---|---|
| Extended addressing mode | no |
| AS-i profile | basic slave (CTT1 input) S-7.4.E additional slave (CTT1 input) S-7.3.E additional slave (CTT1 output) S-7.3.2 |
| basic slave (CTT1 input) | S-7.4.E |
| additional slave (CTT1 input) | S-7.3.E |
| additional slave (CTT1 output) | S-7.3.2 |
| Number of AS-i devices | 1...5 |
Mechanical data
| Weight[g] [g] | 247 |
|---|---|
| Housing | rectangular |
| Type of mounting | backplane mounting |
| Dimensions[mm] [mm] | 124 x 59.3 x 38.4 |
| Materials | housing: PA orange; socket: brass nickel-plated |
Electrical connection
| Module connection | M12 |
|---|
Remarks
| Remarks | For further information please see the operating instructions. |
|---|---|
| Pack quantity | 1 pcs. |
Electrical connection - IO-Link
| Connector | 4 x M12; coding: A |
|---|
Electrical connection - power supply IN
| Connector | 1 x M12; coding: A |
|---|
Electrical connection - power supply OUT
| Connector | 1 x M12; coding: A |
|---|
Customer Reviews
Rated 0 out of 5
0 reviews
Rated 5 out of 5
0
Rated 4 out of 5
0
Rated 3 out of 5
0
Rated 2 out of 5
0
Rated 1 out of 5
0
Be the first to review “IFM AC6000” Cancel reply