Sick SIG200-0A0412200
Network devices | SIG200 | SIG200-0A0412200 | Product category: IO-Link Master | Communication interface: IO-LinkUSBEthernetPROFINETREST API | Supported products: IO-Link DevicesBinary actuatorsBinary…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Network devices | SIG200 | SIG200-0A0412200 | Product category: IO-Link Master | Communication interface: IO-LinkUSBEthernetPROFINETREST API | Supported products: IO-Link DevicesBinary actuatorsBinary switching sensors | Scope of delivery: SIG200-0A04122004x blind plugs (M12) on port S2, S3, S4, P21x blind plug (M8) on port CONFIGMarking labelsQuickstart | Further functions: Web server integratedUSB connection for easy configuration of the SIG200 Sensor Integration Gateway with SOPAS ET, the engineering tool from SICKLogic editor is available for easy configuration of logic functions
Specification
Features
| Product category | IO-Link Master |
|---|---|
| Supported products | IO-Link DevicesBinary actuatorsBinary switching sensors |
| Further functions | Web server integratedUSB connection for easy configuration of the SIG200 Sensor Integration Gateway with SOPAS ET, the engineering tool from SICKLogic editor is available for easy configuration of logic functions |
| Items supplied | SIG200-0A0412200, 4x blind plugs (M12) on port S2, S3, S4, P2, 1x blind plug (M8) on port CONFIG, Marking labels, quickstart |
Mechanics/electronics
| IO-Link | 4 x M12, 5-pin female connector, A-coded |
|---|---|
| Power | 1 x M12, 4-pin plug, A-coded |
| CONFIG | 1 x M8, 4-pin female connector, USB 2.0 (USB-A) |
| Ethernet | 2 x M12, 4-pin female connector, D-coded |
| Supply voltage | 10Â VÂ DCÂ ... 30Â VÂ DCÂ 1) |
| Current consumption | ≤ 175 mA, ≤ 3,000 mA, At supply voltage 24 V DC 2) 3) |
| Optical indicators | 4Â LED green (To the IO-Link ports, Pin4 (C/DI/DO))4Â LED yellow (To the IO-Link ports, Pin2 (DI))2Â LED green (To the Ethernet ports)1Â LED green (For the Power Port)2Â LED dual-color (for bus error and system error communication) |
| S1-S4 pin 1 voltage supply | ≤ 500 mA (VH ≥ VUS - 3 V) 4) |
| S1-S4 pin 4 output current | ≤ 200 mA (Type 3 IEC 61131-2) 4) |
| Power Port pin 4Â output voltage HIGH | Type 1Â IECÂ 61131-2 |
| S1-S4 pin 2Â input voltage | Type 3Â IECÂ 61131-2 |
| S1-S4 pin 4Â input voltage | Type 1Â IECÂ 61131-2 |
| Enclosure rating | IP67 |
| Protection class | III |
| Housing material | Zinc |
| Housing color | Light blue/Black |
| Weight | 520Â g |
| Dimensions (L x W x H) | 213.9 mm x 57 mm x 38.3 mm |
| UL File No. | E497722 |
Interfaces
| Communication interface | IO-Link, USB, Ethernet, PROFINET, REST API |
|---|---|
| Logic editor | ✔ |
| Web server | ✔ |
| Function | The SIG200 Sensor Integration Gateway is an IO-Link master with 4Â configurable ports to which IO-Link device as well as binary switching sensors and actuators can be connected. The gateway data is made available to a PLC or cloud application via the REST API.SIG200 can also be operated as a standalone system by directly configuring simple logic functions across several connected devices via the SOPAS ET user interface. |
| IO-Link version | V1.1, V1.0 |
| Port Class | A |
| Number of IO-Link ports | 4 |
| Transmission type | COM1, COM2, COM3 |
| Operator interfaces | SOPAS ET, the engineering tool for configuration via USB, Additionally, the SIG200 can be configured via the integrated webserver. Default IPÂ adress: 192.168.0.1 |
| MAC address | See product label |
| Number of inputs | Max. 8Â x PNP, type 1Â or 4Â x IO-Link |
| Number of outputs | Max. 4Â x PNP |
| Max. Output frequency | 50Â Hz |
| S1-S4 | 4Â configurable portsPin4 can be used in one of the available port modes: IO-Link, digital input or digital output. An additional digital input signal can be connected using Pin2. (SOPAS ET can be downloaded for free from www.sick.com) |
| LINK/ACT 1Â & 2 | Two Ethernet ports are provided for the network connection |
| CONFIG | Port for configuration via USB with SOPAS ET (SOPAS ET can be downloaded for free from www.sick.com) |
| Conformities | Conformance Class B |
| Network load class | III |
| Initialization time after switch on | 60s (plus additional time for IODD installation) |
Ambient data
| Ambient operating temperature | –40 °C ... +55 °C 1) |
|---|---|
| Ambient temperature, storage | –40 °C ... +75 °C 1) |
| Electromagnetic compatibility (EMC) | ENÂ 61000-6-2:2005-08 / ENÂ 61000-6-3:2007-01 |
| Shock load | ENÂ 60068-2-6 |
Certificates
| EU declaration of conformity | ✔ |
|---|---|
| UK declaration of conformity | ✔ |
| ACMA declaration of conformity | ✔ |
| Moroccan declaration of conformity | ✔ |
| China RoHS | ✔ |
| cULus certificate | ✔ |
| IO-Link certificate | ✔ |
| Profinet certificate | ✔ |
Classifications
| ECLASS 5.0 | 27242208 |
|---|---|
| ECLASS 5.1.4 | 27242608 |
| ECLASS 6.0 | 27242608 |
| ECLASS 6.2 | 27242608 |
| ECLASS 7.0 | 27242608 |
| ECLASS 8.0 | 27242608 |
| ECLASS 8.1 | 27242608 |
| ECLASS 9.0 | 27242608 |
| ECLASS 10.0 | 27242608 |
| ECLASS 11.0 | 27242608 |
| ECLASS 12.0 | 27242608 |
| ETIM 5.0 | EC001604 |
| ETIM 6.0 | EC001604 |
| ETIM 7.0 | EC001604 |
| ETIM 8.0 | EC001604 |
| UNSPSC 16.0901 | 32151705 |