Sick IMS30-20NPSVU2S
Inductive proximity sensors | IMS | IMS30-20NPSVU2S | Special applications: Mobile machines, Zones with coolants and lubricants, Difficult application conditions | Special features: Resistant against…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Inductive proximity sensors | IMS | IMS30-20NPSVU2S | Special applications: Mobile machines, Zones with coolants and lubricants, Difficult application conditions | Special features: Resistant against coolant lubricants, Temperature resistance
Specification
Features
| Housing | Metric |
|---|---|
| Housing | Standard design |
| Thread size | M30Â x 1.5 |
| Diameter | Ø 30 mm |
| Sensing range Sn | 20Â mm |
| Safe sensing range Sa | 16.2Â mm |
| Installation type | Non-flush |
| Switching frequency | 500Â Hz |
| Connection type | Cable, 3-wire, 2Â m |
| Switching output | PNP |
| Switching output detail | PNP |
| Output function | NO |
| Electrical wiring | DC 3-wire |
| Enclosure rating | IP68Â 1)IP69KÂ 2) |
| Special features | Resistant against coolant lubricants, Temperature resistance |
| Special applications | Mobile machines, Zones with coolants and lubricants, Difficult application conditions |
| Items supplied | Mounting nut, brass, nickel-plated (2x) |
Mechanics/electronics
| Supply voltage | 7.2Â VÂ DCÂ ... 60Â VÂ DC |
|---|---|
| Ripple | ≤ 10 % |
| Voltage drop | ≤ 2.5 V 1) |
| Time delay before availability | 100Â ms |
| Hysteresis | 3Â %Â ... 20Â % |
| Reproducibility | ≤ 2 % 2) |
| Temperature drift (of Sr) | ± 10 % |
| EMC | Emitted interference and interference immunity in accordance with Motor Insurance Directive ECE-R10 Rev. 5: E1-Type approvalInterference immunity in accordance with DINÂ ISOÂ 11452-2: 100Â V/mAM vertical 20Â MHz - 800Â MHz; AM horizontal 200Â MHz - 800Â MHz; PM vertical/horizontal 800Â MHz - 2.7Â GHzConducted disturbances in accordance with ISOÂ 7637-2 (pulse/severity/failure criterion 12Â V/failure criterion 24Â V): 1/IV/C/C, 2a/IV/A/A, 2b/IV/C/C, 3a/IV/A/A, 3b/IV/A/A, 4/IV/C/A, 5a/IV/B/B, 5b/IV/B/BENÂ 61000-4-2 ESD: 4Â kV CDÂ /Â 8Â kV ADENÂ 61000-4-3Â HF radiated: 10Â V/mENÂ 61000-4-4Â burst: 2Â kVENÂ 61000-4-5 surge: 0,5Â kV L-to-L, Ri: 2Â Ohm |
| Environmental test | Quick temperature change EN 60068-2-14, Na: TA = –25 °C, TB = 75 °C, t1 = 40 min, t2 = < 10 s, 300 cycles, Delta Sr ≤ 10% |
| Corrosion test | Salt spray test ENÂ 60068-2-52: severity 5, 4Â cycles |
| Continuous current Ia | ≤ 200 mA 3) |
| No load current | ≤ 10 mA |
| Cable material | PUR |
| Conductor size | 0.5 mm² |
| Cable diameter | Ø 5 mm |
| Short-circuit protection | ✔ |
| Power-up pulse protection | ✔ |
| Shock and vibration resistance | Vibration resistance EN 60068-2-6 Fc: 25 g peak (10 Hz ... 2,000 Hz) / –20 °C ... +50 °CShock resistance EN 60068-2-27 Ea: 100 g 11 ms; 3 shocks in every direction of the 3 coordinate axes / –40 °C ... +85 °CContinuous shock resistance EN 60068-2-29 Eb: 40 g 3 ms rise, 7 ms fall / 5,000 shocks in every direction of the 3 coordinate axes / -20 °C ... +50 °CBroadband noise EN 60068-2-64: 15 g rms (5 Hz ... 2,000 Hz) / 8 hours in every direction of the 3 coordinate axes / –40 °C ... +85 °C |
| Ambient operating temperature | –40 °C ... +100 °C |
| Housing material | Stainless steel V2A, DINÂ 1.4305Â / AISI 303 |
| Sensing face material | Plastic, LCP |
| Housing length | 61Â mm |
| Thread length | 43.65Â mm |
| Tightening torque, max. | Typ. 100 Nm |
| Protection class | III |
| UL File No. | E181493 |
Safety-related parameters
| MTTFD | 1,196Â years |
|---|---|
| DCavg | 0Â % |
Reduction factors
| Note | The values are reference values which may vary |
|---|---|
| Stainless steel (V2A, 304) | Approx. 0.78 |
| Aluminum (Al) | Approx. 0.44 |
| Copper (Cu) | Approx. 0.36 |
| Brass (Br) | Approx. 0.46 |
Installation note
| Remark | Associated graphic see "Installation" |
|---|---|
| A | 20Â mm |
| B | 62Â mm |
| C | 30Â mm |
| D | 60Â mm |
| E | 20Â mm |
| F | 160Â mm |
Certificates
| EU declaration of conformity | ✔ |
|---|---|
| UK declaration of conformity | ✔ |
| ACMA declaration of conformity | ✔ |
| Moroccan declaration of conformity | ✔ |
| China RoHS | ✔ |
| CCC certificate | ✔ |
| cULus certificate | ✔ |
| ECE test certificate | ✔ |
Classifications
| ECLASS 5.0 | 27270101 |
|---|---|
| ECLASS 5.1.4 | 27270101 |
| ECLASS 6.0 | 27270101 |
| ECLASS 6.2 | 27270101 |
| ECLASS 7.0 | 27270101 |
| ECLASS 8.0 | 27270101 |
| ECLASS 8.1 | 27270101 |
| ECLASS 9.0 | 27270101 |
| ECLASS 10.0 | 27270101 |
| ECLASS 11.0 | 27270101 |
| ECLASS 12.0 | 27274001 |
| ETIM 5.0 | EC002714 |
| ETIM 6.0 | EC002714 |
| ETIM 7.0 | EC002714 |
| ETIM 8.0 | EC002714 |
| UNSPSC 16.0901 | 39122230 |