Fast delivery within 72 Hours

Sick IMF12-08NPSNC0SX02

Inductive proximity sensors | IMF | IMF12-08NPSNC0SX02 | Housing: Standard design | Special applications: Hygienic and washdown zones, Difficult application conditions, Explosive areas | Sensing range…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

Inductive proximity sensors | IMF | IMF12-08NPSNC0SX02 | Housing: Standard design | Special applications: Hygienic and washdown zones, Difficult application conditions, Explosive areas | Sensing range Sn: 8 mm | Installation type: Non-flush | Electrical wiring: DC 3-wire | Switching output: PNP | Output function: NO | Connection type: Male connector M12, 4-pin | Info: II 3G Ex ec IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X In the framework of directive 2014/34 / EU (ATEX) and DIN EN ISO/IEC 80079-34, we would like to point out that the traceability of the ordered device to your customer is your responsibility (documentation of your customer and associated product data, such as part number, datcode, serial number) | Special features: Resistant to cleaning agents, Visual adjustment indicator, IO-Link

Specification

Features

HousingMetric
HousingStandard design
Thread sizeM12Â x 1
DiameterØ 12 mm
Sensing range Sn8Â mm
Safe sensing range Sa6.48Â mm
Installation typeNon-flush
Switching frequency2,000Â Hz
Connection typeMale connector M12, 4-pin 1)
Switching outputPNP
Switching output detailPNP
Output functionNO
Electrical wiringDC 3-wire
Enclosure ratingIP67Â 2)
Special featuresResistant to cleaning agents, Visual adjustment indicator, IO-Link
Special applicationsHygienic and washdown zones, Difficult application conditions, Explosive areas
Items suppliedMounting nut, V4A stainless steel (2x)Cable housing/cover

Mechanics/electronics

Supply voltage10Â VÂ DCÂ ... 30Â VÂ DC
Ripple≤ 10 %
Voltage drop≤ 2 V 1)
Hysteresis3Â %Â ... 20Â %
Reproducibility≤ 2 % 2) 3)
Temperature drift (of Sr)± 10 %
EMCAccording to ENÂ 60947-5-2
Continuous current Ia≤ 200 mA 4)
No load current≤ 10 mA
Short-circuit protection✔
Power-up pulse protection✔
Shock and vibration resistance100 g / 2 ms / 500 cycles; 150 g / 1 Mio cycles; 10 Hz ... 55 Hz / 1 mm; 55 Hz ... 500 Hz / 60 g
Ambient operating temperature–20 °C ... +85 °C
Housing materialStainless steel V4A, DINÂ 1.4404Â / AISI 316L
Sensing face materialPlastic, LCP
Housing length65Â mm
Thread length43Â mm
Tightening torque, max.Typ. 32 Nm
ATEX markingII 3G Ex ec IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X
Ex area category3G, 3D
Protection classIII
UL File No.E181493

Safety-related parameters

MTTFD1,971Â years
DCavg0Â %
TM (mission time)20Â years

Communication interface

Communication interfaceIO-Link V1.0
Communication Interface detailCOM2 (38,4Â kBaud)
Process data length1Â Byte
Process data structureBit 0Â = Sr reachedBit 1Â = Sa reached

Reduction factors

NoteThe values are reference values which may vary
Stainless steel (V2A, 304)Approx. 0.67
Aluminum (Al)Approx. 0.42
Copper (Cu)Approx. 0.35
Brass (Br)Approx. 0.42

Installation note

RemarkAssociated graphic see "Installation"
A12Â mm
B24Â mm
C12Â mm
D24Â mm
E16Â mm
F64Â mm

Certificates

EU declaration of conformity✔
UK declaration of conformity✔
ACMA declaration of conformity✔
Moroccan declaration of conformity✔
China RoHS✔
ECOLAB certificate✔
FDA certificate✔
cULus certificate✔
IO-Link certificate✔

Classifications

ECLASS 5.027270101
ECLASS 5.1.427270101
ECLASS 6.027270101
ECLASS 6.227270101
ECLASS 7.027270101
ECLASS 8.027270101
ECLASS 8.127270101
ECLASS 9.027270101
ECLASS 10.027270101
ECLASS 11.027270101
ECLASS 12.027274001
ETIM 5.0EC002714
ETIM 6.0EC002714
ETIM 7.0EC002714
ETIM 8.0EC002714
UNSPSC 16.090139122230