Keyence KV-NC4AD
A/D Conversion unit,4-point type. KV-NC4AD. Series: Programmable Logic Controller. Series code: KV-X series
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
A/D Conversion unit,4-point type. KV-NC4AD. Series: Programmable Logic Controller. Series code: KV-X series
Specification
| Model Name |
A/D Conversion unit,4-point type |
|---|---|
| Model Code |
KV-NC4AD |
| Series Title |
Programmable Logic Controller |
| Series Code |
KV-X series |
| Data Sheet URL | |
| CAD URL | |
| Manuals URL | |
| Model |
KV-NC4AD |
| Conversion speed |
80 μs/channel*1 |
| Conversion |
A/D conversion |
| Points |
4 (single end) |
| Range/resolution - Voltage |
1/8000 2.5 mV |
| Range/resolution |
1/4000 2.5 mV |
| Range/resolution - Current |
1/4000 5 μA |
| Conversion precision - Voltage |
±0.3% of F.S. (at 25°C ±5°C 77°F ±9°F)±0.5% of F.S. (at 0 to 55°C 32 to 131°F) |
| Conversion precision |
±0.3% of F.S. (at 0 to 55°C 32 to 131°F) |
| Conversion precision - Current |
±0.4% of F.S. (at 25°C ±5°C 77°F ±9°F)±0.6% of F.S. (at 0 to 55°C 32 to 131°F) |
| Input resistance - Voltage |
5 MΩ |
| Input resistance - Current |
250 Ω |
| Absolute maximum input - Voltage |
±15 V |
| Absolute maximum input - Current |
±30 mA |
| Isolation method - Between analog input |
Isolated (photocoupler, transformer) |
| Isolation method - Between analogu input channels |
No isolation |
| Minimum load resistance |
− |
| Special functions |
Input range switching,temperature fluctuation compensation enabling/disabling,channel skip, scaling, special data offset, peak-/bottom-hold,zero clip, zero shift, comparator,averaging (time-specified, count-specified, moving average),disconnection detection, |