Fast delivery within 72 Hours

Pepperl Fuchs VAN-115/230AC-K16

AS-Interface power supply. AS-Interface power supply, data decoupling, 8 A. UL File Number: E223176. MTBF: 100 a. Reset push-button switch: FUSE mode reset. Power selection switch: changeover switch f…

Request for Quote

Shipping & Delivery

  • Courier delivery

Our courier will deliver to the specified address

5-6 Days

From €20

  • DHL Courier delivery

DHL courier will deliver to the specified address

2-3 Days

From €40

  • Warranty 1 year
  • Free 30-Day returns

Description

AS-Interface power supply. AS-Interface power supply, data decoupling, 8 A. UL File Number: E223176. MTBF: 100 a. Reset push-button switch: FUSE mode reset. Power selection switch: changeover switch for 115 V AC/230 V AC. LED Overload: red LED, flashes in the FUSE mode. LED IR on: red LED:ON: Plug-in jumper position 2-3OFF: Plug-in jumper position 1-2. Plug-in jumper: Position 1-2: Communication ModePosition 2-3: IR addressing. LED AS-i ok: operating display; LED green. Fusing: T8A/250 V AC HBC (not accessible). Capacity factor: > 0.5. Rated operating voltage: nominal: 100 … 120 V AC/220 … 240 V AC (front end selectable)permissible: 85 … 132 V AC/184 … 264 V AC/230 … 375 V DC. Rated operating current: 6,0 A (Switch position 115 V)2.8 A (Switch position 230 V). Supply frequency: 47 … 63 Hz or DC. Efficiency: typ. 92 % (at 230 V AC/8 A). Surge protection: limited to max. 55 V. Short-circuit protection/overload: FUSE Mode (2 … 5 s current, then trips). Current limit: > 8.4 A. Voltage: 30.55 V DC ± 3 %. Current: 8 A. Galvanic isolation: overvoltage category III. Residual ripple: ≤ 50 mVss (500 kHz bandwidth, 50-Ω-measurement with ohmic load). Short-circuit current: 12 … 25 A (max. 5 s). Electromagnetic compatibility: emitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022)noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11. Ambient temperature: -10 … 70 °C (14 … 158 °F) (Measured 25 mm below the device)from 60° C 6W/°C power recovery necessary. Storage temperature: -25 … 85 °C (-13 … 185 °F). Pollution degree: 2. Degree of protection: IP20 according to EN 60529. Protection class: 1 (IEC 60536); Protective conductor connection necessary. Connection: Connection terminals, max. conductor cross-section flexible: 0.5 … 4 mm2fixed: 0.5 … 6 mm2stripped length 7 mm, connector sleeves are permissible. Material: . Housingmetal: . Housing: metal. Mass: approx. 890 g. Dimensions: . Height124 mmWidth91 mmLength102 mm: . Height: 124 mm. Width: 91 mm. Length: 102 mm

Specification

General specifications

UL File NumberE223176
MTBF100 a

Indicators/operating means

Reset push-button switchFUSE mode reset
Power selection switchchangeover switch for 115 V AC/230 V AC
LED Overloadred LED, flashes in the FUSE mode
LED IR onred LED:ON: Plug-in jumper position 2-3OFF: Plug-in jumper position 1-2
Plug-in jumperPosition 1-2: Communication ModePosition 2-3: IR addressing
LED AS-i okoperating display; LED green

Electrical specifications

FusingT8A/250 V AC HBC (not accessible)
Capacity factor> 0.5
Rated operating voltagenominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable)permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC
Rated operating current6,0 A (Switch position 115 V)2.8 A (Switch position 230 V)
Supply frequency47 ... 63 Hz or DC
Efficiencytyp. 92 % (at 230 V AC/8 A)
Surge protectionlimited to max. 55 V

Output

Short-circuit protection/overloadFUSE Mode (2 ... 5 s current, then trips)
Current limit> 8.4 A
Voltage30.55 V DC ± 3 %
Current8 A
Galvanic isolationovervoltage category III
Residual ripple≤ 50 mVss (500 kHz bandwidth, 50-Ω-measurement with ohmic load)
Short-circuit current12 ... 25 A (max. 5 s)

Standard conformity

Electromagnetic compatibilityemitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022)noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11

Ambient conditions

Ambient temperature-10 ... 70 °C (14 ... 158 °F) (Measured 25 mm below the device)from 60° C 6W/°C power recovery necessary
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Pollution degree2

Mechanical specifications

Degree of protectionIP20 according to EN 60529
Protection class1 (IEC 60536); Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2fixed: 0.5 ... 6 mm2stripped length 7 mm, connector sleeves are permissible
Material
Housingmetal
Housingmetal
Massapprox. 890 g
Dimensions
Height124 mmWidth91 mmLength102 mm
Height124 mm
Width91 mm
Length102 mm

Customer Reviews

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Pepperl Fuchs VAN-115/230AC-K16”

Your email address will not be published. Required fields are marked *