Fast delivery within 72 Hours
Pepperl Fuchs 7500-01-AA-STD-UNV-PNO
7500 Series Control Unit, Type Z and Ex pzc. You must purchase an EPV-7500-* vent with the control unit.. Equipment architecture: max. enclosure size 12.7 m3 (450 ft3)For complete technical data, see…
Request for Quote
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
7500 Series Control Unit, Type Z and Ex pzc. You must purchase an EPV-7500-* vent with the control unit.. Equipment architecture: max. enclosure size 12.7 m3 (450 ft3)For complete technical data, see the 7500 Control Unit and 7500-MAN-MV-01 datasheets. Operating mode: fully automatic (FA). Series: 7500. System: Type Z Purge ; Ex pzc Purge. Hazardous environment: gas or dust. Rated voltage: 20 … 30 V DC at 0.1 A 90 … 250 V AC , 50 … 60 Hz at 0.04 A without solenoid valve Supply voltage can be line-to-line or line-to-neutral, single phase OVC II. Power consumption: max. 2.7 W / 7.3 VA without valve. Connection: screw terminals — see manual for specifications on wire size and torque values. Output I: . ConnectionK1, terminals, 1 x NOOutput typeenclosure power contactsContact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A: . Connection: K1, terminals, 1 x NO. Output type: enclosure power contacts. Contact loading: 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A. Output II: . ConnectionK2, terminals, 1 x NOOutput typealarm and control contactsContact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fusedinrush current: 50 A: . Connection: K2, terminals, 1 x NO. Output type: alarm and control contacts. Contact loading: 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fusedinrush current: 50 A. Output III: . ConnectionSV1, terminals, L1 powered contactOutput typesolenoid manifold, contactContact loading0.5 A at 250 V AC , 0.5 A: . Connection: SV1, terminals, L1 powered contact. Output type: solenoid manifold, contact. Contact loading: 0.5 A at 250 V AC , 0.5 A. LED indication: K1: Green – Contact K1 is energized (enclosure contacts) K2: Amber – Contact K2 is energized (alarm/control contacts) P/SV: Blue – Safe pressure P1 (minimum enclosure pressure) P/SV: Amber – Solenoid manifold is energized (purging/pressure compensation). Protective gas supply: compressed air or inert gas, 40 µm filter, free from oil. Pressure requirement: supply pressure: 1.4 … 8.2 bar (20 … 120 psig). Safe pressure: For model 7500-01*:P1 for gas: 0.12 inch w.c. (0.30 mbar)P1 for dust: 0.52 inch w.c. (1.29 mbar)P2: 0.8 inch w.c. (1.99 mbar)P3: 2.5 inch w.c. (6.22 mbar)P4: 4.5 inch w.c. (11.2 mbar)pressure sensing : -0.31 / +0 mbar (-0.125 / +0 in wc)For model 7500-03*:P1 for gas: 0.23 inch w.c. (0.57 mbar)P1 for dust: 0.63 inch w.c. (1.57 mbar)P2: 0.8 inch w.c. (1.99 mbar)P3: 2.5 inch w.c. (6.22 mbar)P4: 4.5 inch w.c. (11.2 mbar) pressure sensing: -0.43 / +0 mbar (0.175 / +0 in wc). Enclosure pressure: For model 7500-01*:0 … 12.9 mbar (0 … 5 in wc)For model 7500-03*:0 … 25.8 mbar (0 … 10 in wc). Electromagnetic compatibility: . Directive 2014/30/EUEN 61326-1:2013: . Directive 2014/30/EU: EN 61326-1:2013. RoHS: . Directive 2011/65/EU (RoHS)EN IEC 63000:2018: . Directive 2011/65/EU (RoHS): EN IEC 63000:2018. Electromagnetic compatibility: EN 61326-3-2:2008, EN 61000-6-2:2005. Emitted interference: FCC CFR 47, part 15, subpart B: 2017 , ICES-003, Issue 6:2016, Class A ITE. Ambient temperature: -40 … 50 °C (-40 … 122 °F) at T6 -40 … 65 °C (-40 … 149 °F) at T5 -40 … 70 °C (-40 … 158 °F) at T4. Storage temperature: -40 … 80 °C (-40 … 176 °F). Relative humidity: 5 … 90 %, non-condensing. Altitude: max. 2000 m. Vibration resistance: 5 … 100 Hz , 1 g, 12 m/s2, all axes. Impact resistance: 30 g, 11 ms, all axes. Connection type: electrical: 2 x 1/2 inch NPTF (open from factory) 1 x M12 opening (plugged from factory) pneumatic: high-pressure port – 1/8 in NPTF, low-pressure port – 1/8 in NPTF. Degree of protection: Type 4X , IP66. Material: Lens: Makrolon® GP-V polycarbonate Screws: AISI 316 (1.4401), 304, or 18-8 stainless steel Housing: A380, A356, or 6061-T6 aluminumMounting gasket: Bisco® HT-800 medium cellular siliconeMounting tabs: SAE 304 stainless steelM12 plug: 6061-T6 aluminum. Mass: 710 g (1 lb 10 oz). Dimensions: 150 x 100 x 50 mm (5.9 x 4 x 2 in). Certificate: . Marking II 3 G Ex ec mc nC [pzc Gc] IIC T6…T4 Gc [exsign] II 3 D Ex mc tc [pzc Dc] IIIC T60 °C … T80 °C Dc: . Marking: II 3 G Ex ec mc nC [pzc Gc] IIC T6…T4 Gc [exsign] II 3 D Ex mc tc [pzc Dc] IIIC T60 °C … T80 °C Dc. Directive conformity: . Directive 2014/34/EUIEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 , IEC/EN 60079-18 , IEC/EN 60079-31 Supplements: EN 61010-1:2010: . Directive 2014/34/EU: IEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 , IEC/EN 60079-18 , IEC/EN 60079-31 Supplements: EN 61010-1:2010. UL approval: . cULusClass I, Division 2, Groups A, B, C, D T6 … T4 Class II, Division 2, Groups F, G T6 … T4: . cULus: Class I, Division 2, Groups A, B, C, D T6 … T4 Class II, Division 2, Groups F, G T6 … T4. IECEx approval: Ex ec mc nC [pzc Gc] IIC T6…T4 Gc Ex mc tc [pzc Dc] IIIC T60 °C … T80 °C Dc. Supplementary information: Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Specification
General specifications
| Equipment architecture | max. enclosure size 12.7 m3 (450 ft3)For complete technical data, see the 7500 Control Unit and 7500-MAN-MV-01 datasheets |
|---|---|
| Operating mode | fully automatic (FA) |
| Series | 7500 |
| System | Type Z Purge ; Ex pzc Purge |
| Hazardous environment | gas or dust |
Supply
| Rated voltage | 20 ... 30 V DC at 0.1 A 90 ... 250 V AC , 50 ... 60 Hz at 0.04 A without solenoid valve Supply voltage can be line-to-line or line-to-neutral, single phase OVC II |
|---|---|
| Power consumption | max. 2.7 W / 7.3 VA without valve |
Electrical specifications
| Connection | screw terminals -- see manual for specifications on wire size and torque values |
|---|
Output
| Output I | |
|---|---|
| ConnectionK1, terminals, 1 x NOOutput typeenclosure power contactsContact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A | |
| Connection | K1, terminals, 1 x NO |
| Output type | enclosure power contacts |
| Contact loading | 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A |
| Output II | |
| ConnectionK2, terminals, 1 x NOOutput typealarm and control contactsContact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fusedinrush current: 50 A | |
| Connection | K2, terminals, 1 x NO |
| Output type | alarm and control contacts |
| Contact loading | 5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fusedinrush current: 50 A |
| Output III | |
| ConnectionSV1, terminals, L1 powered contactOutput typesolenoid manifold, contactContact loading0.5 A at 250 V AC , 0.5 A | |
| Connection | SV1, terminals, L1 powered contact |
| Output type | solenoid manifold, contact |
| Contact loading | 0.5 A at 250 V AC , 0.5 A |
Indicators/settings
| LED indication | K1: Green - Contact K1 is energized (enclosure contacts) K2: Amber - Contact K2 is energized (alarm/control contacts) P/SV: Blue - Safe pressure P1 (minimum enclosure pressure) P/SV: Amber - Solenoid manifold is energized (purging/pressure compensation) |
|---|
Pneumatic parameters
| Protective gas supply | compressed air or inert gas, 40 µm filter, free from oil |
|---|---|
| Pressure requirement | supply pressure: 1.4 ... 8.2 bar (20 ... 120 psig) |
| Safe pressure | For model 7500-01*:P1 for gas: 0.12 inch w.c. (0.30 mbar)P1 for dust: 0.52 inch w.c. (1.29 mbar)P2: 0.8 inch w.c. (1.99 mbar)P3: 2.5 inch w.c. (6.22 mbar)P4: 4.5 inch w.c. (11.2 mbar)pressure sensing : -0.31 / +0 mbar (-0.125 / +0 in wc)For model 7500-03*:P1 for gas: 0.23 inch w.c. (0.57 mbar)P1 for dust: 0.63 inch w.c. (1.57 mbar)P2: 0.8 inch w.c. (1.99 mbar)P3: 2.5 inch w.c. (6.22 mbar)P4: 4.5 inch w.c. (11.2 mbar) pressure sensing: -0.43 / +0 mbar (0.175 / +0 in wc) |
| Enclosure pressure | For model 7500-01*:0 ... 12.9 mbar (0 ... 5 in wc)For model 7500-03*:0 ... 25.8 mbar (0 ... 10 in wc) |
Directive conformity
| Electromagnetic compatibility | |
|---|---|
| Directive 2014/30/EUEN 61326-1:2013 | |
| Directive 2014/30/EU | EN 61326-1:2013 |
| RoHS | |
| Directive 2011/65/EU (RoHS)EN IEC 63000:2018 | |
| Directive 2011/65/EU (RoHS) | EN IEC 63000:2018 |
Conformity
| Electromagnetic compatibility | EN 61326-3-2:2008, EN 61000-6-2:2005 |
|---|---|
| Emitted interference | FCC CFR 47, part 15, subpart B: 2017 , ICES-003, Issue 6:2016, Class A ITE |
Ambient conditions
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) at T6 -40 ... 65 °C (-40 ... 149 °F) at T5 -40 ... 70 °C (-40 ... 158 °F) at T4 |
|---|---|
| Storage temperature | -40 ... 80 °C (-40 ... 176 °F) |
| Relative humidity | 5 ... 90 %, non-condensing |
| Altitude | max. 2000 m |
| Vibration resistance | 5 ... 100 Hz , 1 g, 12 m/s2, all axes |
| Impact resistance | 30 g, 11 ms, all axes |
Mechanical specifications
| Connection type | electrical: 2 x 1/2 inch NPTF (open from factory) 1 x M12 opening (plugged from factory) pneumatic: high-pressure port - 1/8 in NPTF, low-pressure port - 1/8 in NPTF |
|---|---|
| Degree of protection | Type 4X , IP66 |
| Material | Lens: Makrolon® GP-V polycarbonate Screws: AISI 316 (1.4401), 304, or 18-8 stainless steel Housing: A380, A356, or 6061-T6 aluminumMounting gasket: Bisco® HT-800 medium cellular siliconeMounting tabs: SAE 304 stainless steelM12 plug: 6061-T6 aluminum |
| Mass | 710 g (1 lb 10 oz) |
| Dimensions | 150 x 100 x 50 mm (5.9 x 4 x 2 in) |
Data for application in connection with hazardous areas
| Certificate | |
|---|---|
| Marking II 3 G Ex ec mc nC [pzc Gc] IIC T6...T4 Gc [exsign] II 3 D Ex mc tc [pzc Dc] IIIC T60 °C ... T80 °C Dc | |
| Marking | II 3 G Ex ec mc nC [pzc Gc] IIC T6...T4 Gc [exsign] II 3 D Ex mc tc [pzc Dc] IIIC T60 °C ... T80 °C Dc |
| Directive conformity | |
| Directive 2014/34/EUIEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 , IEC/EN 60079-18 , IEC/EN 60079-31 Supplements: EN 61010-1:2010 | |
| Directive 2014/34/EU | IEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 , IEC/EN 60079-18 , IEC/EN 60079-31 Supplements: EN 61010-1:2010 |
International approvals
| UL approval | |
|---|---|
| cULusClass I, Division 2, Groups A, B, C, D T6 ... T4 Class II, Division 2, Groups F, G T6 ... T4 | |
| cULus | Class I, Division 2, Groups A, B, C, D T6 ... T4 Class II, Division 2, Groups F, G T6 ... T4 |
| IECEx approval | Ex ec mc nC [pzc Gc] IIC T6...T4 Gc Ex mc tc [pzc Dc] IIIC T60 °C ... T80 °C Dc |
General information
| Supplementary information | Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
|---|

Reviews