Fast delivery within 72 Hours
Yaskawa GA800 CONFIGURED
Yaskawa’s GA800 configured package is designed for tough industrial environments. It is rugged and reliable. A variety of enclosure options are available including NEMA 1, NEMA 12 or NEMA 3R
Shipping & Delivery
-
Courier delivery
Our courier will deliver to the specified address
5-6 Days
From €20
-
DHL Courier delivery
DHL courier will deliver to the specified address
2-3 Days
From €40
-
Warranty 1 year
-
Free 30-Day returns
Description
Configured Product for GA800 Drive The GA800 Configured package provides a GA800 in a UL Type 1 or UL Type 12 or UL Type 3R enclosure, with space for several commonly used options, such as reactors, circuit breakers, etc. The GA800 Configured Package has been designed for flexibility in providing the features and options commonly requested. This Configured package is designed for tough industrial environments. It is rugged and reliable. A variety of enclosure options provide the right environmental protection.
Specification
| C - 65kAIC Circuit Breaker |
65kA |
|---|---|
| M - 100kAIC Circuit Breaker |
100kA |
| D - Disconnect |
100kA |
| E - Standard Circuit Breaker |
All 240V: 25kA Normal Duty 480V B002 through B156: 18kA Normal Duty 480V B180 through B720: 35kA Heavy Duty 480V B002 through B180: 18kA Heavy Duty 480V B240 through B590: 35kA |
| None of the options above |
Varies by rating. Consult Factory |
| Overload Capacity |
150% for 60 sec. (HD), 110% for 60 sec. (ND) |
| Output Frequency |
0~590 Hz |
| Control Methods |
Open and Closed Loop Current Vector; Open and Closed Loop V/f |
| Motor Types |
Induction Surface Permanent Magnet Interior Permanent Magnet Synchronous Reluctance |
| Ambient Operating Temperature |
-10 to +40°C |
| Global Certification |
UL, CSA, RoHS |
| Functional Safety |
Safe Torque Off, SIL3 according to IEC 62061, PLe according to ISO 13849-1 |
| Standard I/O |
(8) multi-function digital inputs (24Vdc) (3) multi-function analog inputs (0 +/- 10 VDC, 4-20 mA) (1) multi-function pulse inputs (2) Safe Torque Off inputs (1) fault relay output (form C) (3) multi-function relay outputs (form A) (2) multi-function analog output (0 +/- 10 VDC, 4-20mA) (1) multi-function pulse output |
| I/O Expansion |
(3) Analog Inputs -10 to +10V, 13 bit plus sign, 4 to 20mA (16) Digital Inputs (2) Analog Outputs (-10 to +10V, 11 bit magnitude) (8) Digital Outputs (6 transistor, 2 relay) |
| Feedback |
Incremental Absolute (Stegmann, Heidenhain, Resolver) |
| Network Communication |
Standard: Modbus RTU, RS-485, 115 kbps Optional: EtherNet/IP, DeviceNet, Modbus TCP/IP, PROFINET, PROFIBUS-DP |
| Speed Control Range |
1500:1 Closed Loop Vector (IM and PM Motors) 200:1 Open Loop Vector (IM Motors) 100:1 Open Loop Vector (PM Motors) |
| Speed Control Accuracy |
≤ 0.02%: Closed Loop Vector; ≤ 0.2%; Open Loop Vector |
| Speed Response |
≥ 50 Hz: Closed Loop Vector (Induction Motors) ≥ 250 Hz: Closed Loop Vector (PM Motors) ≥ 20 Hz: Open Loop Vector (Induction Motors) ≥ 40 Hz: Open Loop Vector (PM Motors) |
| Function Block Diagrams |
Up to 200 connections, 500us program scan time |